| 2022-03-07 09:37:01 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22010878 |
| | 3/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT COMPLETE SPECS FOR THE NEW RANGE THAT SHOW |
| | THE TOTAL BTU LOAD AND LISTING OF THE APPLIANCE- SEC. |
| | G2447.1 FBC RES. |
| | |
| | 2) THE SUBMITTED CONTRACT DOES NOT APPEAR TO INCLUDE |
| | THE COST OF THE RANGE. TOTAL PERMIT VALUE IS BASED ON |
| | COSTS OF LABOR, MATERIAL, EQUIPMENT AND APPLIANCES- |
| | SEC. 109.3 WPB. |
| | |
| | 3) GAS RISER: |
| | A) PROVIDE THE TOTAL BTU LOAD OF THE NEW RANGE AND THE |
| | TOTAL DEVELOPED LENGTH OF THE SYSTEM- SEC. G2413.4.1 |
| | FBC RES. |
| | B) SHOW THE INPUT AND OUTPUT GAS PRESSURE AT THE |
| | REGULATOR- SEC. G2421.2 FBC RES. |
| | |
| | 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW |
| | RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. |
| | G2407.1 FBC RES. |
| | |
| | 5) CLARIFY- EXISTING OR NEW EXHAUST VENTILATION SYSTEM? |
| | PROVIDE DETAILS FOR NEW EXHAUST HOOD AND DUCT |
| | INSTALLATIONS- SEE SECS. M1503.1- 1503.4 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |