| 2022-04-16 15:08:43 | NFIP PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| | |
| | 2ND REVIEW |
| | |
| | FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NEW GENERAL COMMENTS: |
| | |
| | SEE FILE NAMED: PRODUCT APPROVAL-FLOOD VENT IN THE |
| | SUPPORTING DOCUMENTS FOR COMMENTS 1 & 2 BELOW: |
| | |
| | 1. SEPERATE THE ICC-ES REPORT FROM PRODUCT APPROVAL |
| | FL15822-R7 AND UPLOAD EACH DOCUMENT SEPERATELY. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 2. PRODUCT APPROVAL FL15822-R7 IS MISSING THE |
| | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS. |
| | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | NEW ELEVATION CERTIFICATE COMMENTS: |
| | |
| | 3. LINE A6. PROVIDE A PHOTOGRAPH OF THE INSTALLED FLOOD |
| | VENT MODEL 1540-521 (STACKER). |
| | |
| | 4. LINE A9. REQUIRED DATA IS THE TOTAL SQUARE INCHES OF |
| | THE FLOOD VENTS: THIS SHOULD BE 500 SQ/IN PER TABLE 1 |
| | OF THE ICC-ES EVALUATION REPORT. |
| | |
| | 5. LINE C2 (E). LOWEST ELEVATION OF EQUIPMENT SERVICING |
| | THE BUILDING IS THE AIR HANDLER LOCATED IN THE HVAC |
| | CLOSET INSIDE THE GARAGE. |
| | BOTTOM OF EQUIPMENT SHAL BE AT OR ABOVE THE DFE OF 8.0' |
| | NAVD. |
| | ENTER THIS INFORMATIUON IN THE COMMENTS AREA OF SECTION |
| | D. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |