| Notes |
| Date |
Text |
| 2022-04-04 10:33:28 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. V7 FPC 403.1 MINIMUM NUMBER OF FIXTURES - I WAS | | | UNABLE TO FIND THE OCCUPANT LOAD. PLEASE PROVIDE THE | | | OCCUPANT LOAD FOR DETERMINING THE MINIMUM NUMBER OF | | | FIXTURES. | | | | | | 2. V7 FPC 607.1.1 TEMPERATURE LIMITING MEANS ? THE | | | THERMOSTAT ON THE WATER HEATER CANNOT BE THE LIMIT FOR | | | HOT WATER DELIVERY. PLEASE PROVIDE A DETAIL FOR | | | SOMETHING OTHER THAN THE THERMOSTAT ON THE WATER HEATER | | | EITHER AT THE WATER HEATERS OR AT EACH FIXTURE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|