| Date |
Text |
| 2022-04-19 15:58:26 | BUILD OUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE WALL FINISH SURROUNDING THE TOILET |
| | TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 2) PLEASE SHOW THE WALLS AROUND THE MOP SINK TO COMPLY |
| | WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 3) PLEASE SHOW THE EXISTING TENANT SEPARATION WALL |
| | HOURLY FIRE RATING IF ANY FBC 508.1 |
| | |
| | 4) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER |
| | HOLDER DIMENSIONS FROM THE FACE OF THE TOILET PER FBC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 5) PLEASE SHOW THE TOILET REAR GRAB BAR DIMENSIONS FROM |
| | THE CENTER OF THE TOILET NOT FROM THE WALL PER FBC |
| | 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 6) PLEASE SHOW THE EXISTING OCCUPANCY CLASSIFICATION. |
| | |
| | |
| | |
| | |