| 2022-02-09 14:56:49 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22010862 |
| | ADD: 900 CHARLOTTE AVE |
| | CONT: WINFREE CONTRACTING, INC. |
| | TEL: 561-262-2687 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 09TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S1: |
| | |
| | 1A) PLEASE REVIEW THE WIND DESIGN CRITERIA FOR WIND. |
| | THE WIND EXPOSURE IS STATED AS A B EXPOSURE. PLEASE |
| | REVIEW THE OPEN WATER TO THE NORTHWEST EXPOSURE WHEN |
| | PROJECTING A VECTOR OUT OVER THE WATER THERE IS |
| | APPROXIMATELY 6,000 FEET OF CLEAR WATER, IT ONLY TAKES |
| | 5,000 FT TO PUT THIS SITE INTO AN EXPOSURE D, THE ONLY |
| | QUALIFYING DISTANCE IS ON THAT SAME VECTOR WE MEASURE |
| | THE DISTANCE FORM YOUR SITE TO THE WATER LINE. |
| | WHEN DOING SO IF WE REACH THE WATER LINE BEFORE 600 FT, |
| | IT WOULD KICK IT INTO AN EXPOSURE D. THE DISTANCE TO |
| | THE WATERLINE IS APPROXIMATELY 1,000 FEET, PUTTING THIS |
| | A VERY HIGH EXPOSURE C. |
| | |
| | |
| | 1B) WITH THE NEW EXPOSURE PLEASE APPLY THE ADJUSTMENT |
| | FACTORS FOR HEIGHT AND EXPOSURE TO THE SUBMITTED ROOF |
| | AND WALL ZONES. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR |
| | HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 1C) THE COMPONENTS AND CLADDING PRESSURE CHART FOR ROOF |
| | AND WALL ZONES, PLEASE SPECIFY THESE PRESSURES ARE IN |
| | VASD, SERVICE LOADS, SINCE THE PRODUCT APPROVALS ARE IN |
| | VASD. THANK YOU. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1D) BELOW THE COMPONENTS & CLADDING PRESSURE CHART |
| | THERE IS A ROOF & WALL ZONE FIGURE SHOWING ROOF ZONES |
| | AND WALL ZONES BOTH SHOW THE CORNER ZONES FOR THE ROOF |
| | AND WALLS, WHAT IS MISSING IS THE VALUE |
| | O F ?H?, THERE IS NO ELEVATION VIEW OF THE STRUCTURE. |
| | |
| | 1E) SINCE THERE IS NO ELEVATIONS OF THE SIDES OF THE |
| | BUILDING AND THE LOCATION OF THE MAN DOOR, IF IT IS 3 |
| | FEET WIDE OR A PAIR OF DOORS 6 FEET WIDE DOOR, IN SWING |
| | OR OUT-SWING AND IN WALL ZONE 4 OR 5. THE SAME ISSUE IS |
| | WITH THE ROLL UP DOOR. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1F) EXTERIOR DOOR FLEMING-BARON FL14237-R5 PAGE 4 OF 16 |
| | PLEASE IDENTIFY IF THE DOOR IS A SINGLE OR PAIR, |
| | IN-SWING OR OUT, LATCHING MECHANISM. DOOR SERIES, |
| | GAUGE, MAX SIZE, MIN. THROW (IN.) AND THE MINIMUM LATCH |
| | STRENGTH (LBF). |
| | |
| | 1G) BEST STEEL ROLL-UP DOOR. NOA 19-1015.15, PAGE 3OF 4 |
| | PLEASE IDENTIFY JAMB TYPE CONNECTION, OPENING WIDTH AND |
| | ASSOCIATED PRESSURES. 107.2.1.2. ADDITIONAL INFORMATION |
| | REQUIRED TO DETERMINE CODE COMPLIANCE. |
| | |
| | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |