Plan Review Notes
Plan Review Notes For Permit 22010862
Permit Number 22010862
Review Stop B
Sequence Number 1
Notes
Date Text
2022-02-09 14:56:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22010862
 ADD: 900 CHARLOTTE AVE
 CONT: WINFREE CONTRACTING, INC.
 TEL: 561-262-2687
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 09TH/2022
 ACTION: DENIED
  
 1) SHEET S1:
  
 1A) PLEASE REVIEW THE WIND DESIGN CRITERIA FOR WIND.
 THE WIND EXPOSURE IS STATED AS A B EXPOSURE. PLEASE
 REVIEW THE OPEN WATER TO THE NORTHWEST EXPOSURE WHEN
 PROJECTING A VECTOR OUT OVER THE WATER THERE IS
 APPROXIMATELY 6,000 FEET OF CLEAR WATER, IT ONLY TAKES
 5,000 FT TO PUT THIS SITE INTO AN EXPOSURE D, THE ONLY
 QUALIFYING DISTANCE IS ON THAT SAME VECTOR WE MEASURE
 THE DISTANCE FORM YOUR SITE TO THE WATER LINE.
 WHEN DOING SO IF WE REACH THE WATER LINE BEFORE 600 FT,
 IT WOULD KICK IT INTO AN EXPOSURE D. THE DISTANCE TO
 THE WATERLINE IS APPROXIMATELY 1,000 FEET, PUTTING THIS
 A VERY HIGH EXPOSURE C.
  
  
 1B) WITH THE NEW EXPOSURE PLEASE APPLY THE ADJUSTMENT
 FACTORS FOR HEIGHT AND EXPOSURE TO THE SUBMITTED ROOF
 AND WALL ZONES. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 1C) THE COMPONENTS AND CLADDING PRESSURE CHART FOR ROOF
 AND WALL ZONES, PLEASE SPECIFY THESE PRESSURES ARE IN
 VASD, SERVICE LOADS, SINCE THE PRODUCT APPROVALS ARE IN
 VASD. THANK YOU. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1D) BELOW THE COMPONENTS & CLADDING PRESSURE CHART
 THERE IS A ROOF & WALL ZONE FIGURE SHOWING ROOF ZONES
 AND WALL ZONES BOTH SHOW THE CORNER ZONES FOR THE ROOF
 AND WALLS, WHAT IS MISSING IS THE VALUE
 O F ?H?, THERE IS NO ELEVATION VIEW OF THE STRUCTURE.
  
 1E) SINCE THERE IS NO ELEVATIONS OF THE SIDES OF THE
 BUILDING AND THE LOCATION OF THE MAN DOOR, IF IT IS 3
 FEET WIDE OR A PAIR OF DOORS 6 FEET WIDE DOOR, IN SWING
 OR OUT-SWING AND IN WALL ZONE 4 OR 5. THE SAME ISSUE IS
 WITH THE ROLL UP DOOR. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1F) EXTERIOR DOOR FLEMING-BARON FL14237-R5 PAGE 4 OF 16
 PLEASE IDENTIFY IF THE DOOR IS A SINGLE OR PAIR,
 IN-SWING OR OUT, LATCHING MECHANISM. DOOR SERIES,
 GAUGE, MAX SIZE, MIN. THROW (IN.) AND THE MINIMUM LATCH
 STRENGTH (LBF).
  
 1G) BEST STEEL ROLL-UP DOOR. NOA 19-1015.15, PAGE 3OF 4
 PLEASE IDENTIFY JAMB TYPE CONNECTION, OPENING WIDTH AND
 ASSOCIATED PRESSURES. 107.2.1.2. ADDITIONAL INFORMATION
 REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  