| Plan Review Notes For Permit 22010849 |
| Permit Number |
22010849 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-01 07:58:41 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, WPB AMENDMENTS TO FBC B (FIGURE) | | | 1609.3.1 PLEASE CORRECT THE WIND SPEED INDICATED ON | | | PLAN SHEET A-2.0 (150 MPH). PLAN SHEET S-001, DESIGN | | | CRITERIA, CORRECTLY INDICATES THE WIND SPEED AT 170 | | | MPH. PLEASE CORRECT THE WIND SPEED ON PLAN SHEET A-2.0 | | | FROM 150 MPH TO 170 MPH. | | | | | | 2.) FBC B 107.2.1, PLAN SHEET S-304 IS MISSING. PLAN | | | SHEET S-304 IS REFERENCED IN SEVERAL AREAS ON PLANS. | | | | | | 3.) FBC B 107.2.1, PLAN SHEET A-2.0 INDICATES ROOF TILE | | | PRODUCT APPROVAL #FL 11651.15, BUT PLAN SHEET A-2.1 | | | INDICATES ROOF TILE PRODUCT APPROVAL #FL 28111.1. | | | PLEASE CORRECT PLANS TO INDICATE THE CHOSEN ROOF TILE | | | TO BE USED. | | | | | | 4.) FBC B 107.2.1, PROVIDE A TIE BEAM SCHEDULE. |
|