Plan Review Notes
Plan Review Notes For Permit 22010840
Permit Number 22010840
Review Stop M
Sequence Number 2
Notes
Date Text
2022-04-29 16:29:14THE FOLLOWING COMMENTS HAVE BEEN ADDRESS IN THE
 ORIGINAL MASTER PERMIT. ME
  
  
 2ND REVIEW FMC
 PERMIT: 22010840
  
 CODES IN EFFECT: 2017
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS PERMIT IS FOR THE ROASTER?S EXHAUST, PLEASE
 COMPLETE EVERYTHING NEEDED FOR THE ROASTER?S EXHAUST ON
 THIS PERMIT SO WE CAN CONTINUE TO THE 2ND PHASE OF THE
 PROJECT.
  
 2) SHEET M2.0: PLEASE PROVIDE THE SPECIFICATIONS
 INCLUDING THE CFM?S AND A DETAIL DRAWING OF THE EF-4
 FAN AND DUCT ASSEMBLY. FBC 107.2.1
  
 3) SHEET M2.0: KEYNOTE 20 INDICATES THE L-2 LOUVER WILL
 HAVE A VELOCITY OF 2,000 FPM BUT THE DRAWING SHOWS THE
 12 INCH DUCT WORK ATTACHED TO THE LOUVER WILL HAVE A
 VELOCITY OF 5,730 FPM, PLEASE EXPLAIN THE DIFFERENCE IN
 VELOCITIES. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  