| Plan Review Notes For Permit 22010840 |
| Permit Number |
22010840 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-29 16:29:14 | THE FOLLOWING COMMENTS HAVE BEEN ADDRESS IN THE | | | ORIGINAL MASTER PERMIT. ME | | | | | | | | | 2ND REVIEW FMC | | | PERMIT: 22010840 | | | | | | CODES IN EFFECT: 2017 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS PERMIT IS FOR THE ROASTER?S EXHAUST, PLEASE | | | COMPLETE EVERYTHING NEEDED FOR THE ROASTER?S EXHAUST ON | | | THIS PERMIT SO WE CAN CONTINUE TO THE 2ND PHASE OF THE | | | PROJECT. | | | | | | 2) SHEET M2.0: PLEASE PROVIDE THE SPECIFICATIONS | | | INCLUDING THE CFM?S AND A DETAIL DRAWING OF THE EF-4 | | | FAN AND DUCT ASSEMBLY. FBC 107.2.1 | | | | | | 3) SHEET M2.0: KEYNOTE 20 INDICATES THE L-2 LOUVER WILL | | | HAVE A VELOCITY OF 2,000 FPM BUT THE DRAWING SHOWS THE | | | 12 INCH DUCT WORK ATTACHED TO THE LOUVER WILL HAVE A | | | VELOCITY OF 5,730 FPM, PLEASE EXPLAIN THE DIFFERENCE IN | | | VELOCITIES. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|