Plan Review Notes
Plan Review Notes For Permit 22010840
Permit Number 22010840
Review Stop G
Sequence Number 2
Notes
Date Text
2022-04-11 14:57:051ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22010840
 2/25/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST
 REVIEW LISTED BELOW STILL EXISTS. NO RESPONSE TO THE
 COMMENT WAS PROVIDED.
  
 1) THE BUILDING OFFICIAL ROBERT BROWN HAS REVIEWED THE
 LETTER FROM THE EOR- BRUCE M. CIARLARIELLO PE AND HAS
 DETERMINED IT IS NOT A COMPLETE RATIONAL ANALYSIS FOR
 THE COFFEE ROASTER EXHAUST/VENT SYSTEM AS WAS AGREED TO
 BE PROVIDED BY THE EOR AT THE SITE MEETING. MR. BROWN
 HAS MADE A SECOND REQUEST IN AN EMAIL TO
 MR.CIARLARIELLO FOR THE COMPLETE RATIONAL ANALYSIS, AND
 ALSO FOR A SIGNED COPY OF THE LETTER FROM RAY GARNER OF
 NORDFAB DUCTING. PLEASE NOTE THAT FINAL GAS APPROVAL
 FOR THE SYSTEM IS CONTINGENT ON APPROVAL OF THE
 EXHAUST/VENT SYSTEM- SECS. 107.2.1 & 107.2.1.2 WPB.
  
 NEW COMMENT BASED ON RESUBMITTED PLANS.
  
 1) SHEET M2.0: NEW PLAN NOTE #18 STATES THE EXHAUST
 SYSTEM FALLS UNDER CATEGORY III PER TABLE 503.4 TYPE B
 VENT. PLEASE NOTE THE FOLLOWING:
  
 A) TABLE 503.8 INDICATES A CATEGORY III VENT SYSTEM IS-
 "AS SPECIFIED OR FURNISHED BY MANUFACTURERS OF LISTED
 APPLIANCES (SECTIONS 503.4.1, 503.4.2)". IT APPEARS THE
 SYSTEM SHOWN ON THE PLAN IS DESIGNED BY THE ENGINEER
 AND NOT BY THE MANUFACTURER WHICH IMPLIES THE REFERENCE
 TO THE TABLE IS INCORRECT. ALSO, THE SECTIONS
 REFERENCED IN THE TABLE ARE NOT APPLICABLE- SECTION
 503.4.1 PLASTIC PIPING- NOT APPLICABLE BECAUSE THE DUCT
 IS METAL. SECTION. 503.4.2 STATES- "SPECIAL GAS VENT
 SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL 1738
 AND INSTALLED IN ACCORDANCE WITH THE SPECIAL GAS VENT
 MANUFACTURER'S INSTRUCTIONS"- NOT APPLICABLE BECAUSE
 THE EXHAUST SYSTEM IS NOT A UL 1738 LISTED AND LABELED
 SPECIAL GAS VENT.
 B) TYPE B VENTS SHALL BE LISTED IN ACCORDANCE WITH UL
 441 PER SEC. 503.6.1 FBC FG. B VENTS ARE DOUBLE WALL-
 THE PLAN INDICATES AN UNLISTED SINGLE WALL GAS VENT IS
 BEING INSTALLED. PLEASE NOTE THAT TABLE 503.4 SPECIFIES
 B VENT TO BE USED ONLY FOR LISTED CATEGORY I
 APPLIANCES, LISTED APPLIANCES EQUIPPED WITH DRAFT HOOD,
 AND APPLIANCES LISTED FOR USE WITH TYPE B GAS VENT.
 NOTE #18 INDICATES THE ROASTERS ARE CATEGORY III
 APPLIANCES.
  
 2) M2.0: IT APPEARS A NEW FRESH AIR DUCT AND A NEW
 IN-LINE EXHAUST FAN ARE TO BE CONNECTED TO THE COFFEE
 ROASTER'S 18-INCH MAIN EXHAUST DUCT. A) PROVIDE AN
 EQUIPMENT SCHEDULE FOR THE FAN AND A PRODUCT SUBMITTAL-
 SEC. 305.1 FBC FG. B) PROVIDE A SEQUENCE OF OPERATION
 FOR THE FAN- SEC. 503.3 & 503.6 FBC FG. C) REFER TO
 COMMENT #1 ABOVE AND PROVIDE EVIDENCE THAT INSTALLATION
 OF THE FAN IS CONSISTENT WITH THE MANUFACTURER'S
 SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  