| 2022-04-11 14:57:05 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22010840 |
| | 2/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST |
| | REVIEW LISTED BELOW STILL EXISTS. NO RESPONSE TO THE |
| | COMMENT WAS PROVIDED. |
| | |
| | 1) THE BUILDING OFFICIAL ROBERT BROWN HAS REVIEWED THE |
| | LETTER FROM THE EOR- BRUCE M. CIARLARIELLO PE AND HAS |
| | DETERMINED IT IS NOT A COMPLETE RATIONAL ANALYSIS FOR |
| | THE COFFEE ROASTER EXHAUST/VENT SYSTEM AS WAS AGREED TO |
| | BE PROVIDED BY THE EOR AT THE SITE MEETING. MR. BROWN |
| | HAS MADE A SECOND REQUEST IN AN EMAIL TO |
| | MR.CIARLARIELLO FOR THE COMPLETE RATIONAL ANALYSIS, AND |
| | ALSO FOR A SIGNED COPY OF THE LETTER FROM RAY GARNER OF |
| | NORDFAB DUCTING. PLEASE NOTE THAT FINAL GAS APPROVAL |
| | FOR THE SYSTEM IS CONTINGENT ON APPROVAL OF THE |
| | EXHAUST/VENT SYSTEM- SECS. 107.2.1 & 107.2.1.2 WPB. |
| | |
| | NEW COMMENT BASED ON RESUBMITTED PLANS. |
| | |
| | 1) SHEET M2.0: NEW PLAN NOTE #18 STATES THE EXHAUST |
| | SYSTEM FALLS UNDER CATEGORY III PER TABLE 503.4 TYPE B |
| | VENT. PLEASE NOTE THE FOLLOWING: |
| | |
| | A) TABLE 503.8 INDICATES A CATEGORY III VENT SYSTEM IS- |
| | "AS SPECIFIED OR FURNISHED BY MANUFACTURERS OF LISTED |
| | APPLIANCES (SECTIONS 503.4.1, 503.4.2)". IT APPEARS THE |
| | SYSTEM SHOWN ON THE PLAN IS DESIGNED BY THE ENGINEER |
| | AND NOT BY THE MANUFACTURER WHICH IMPLIES THE REFERENCE |
| | TO THE TABLE IS INCORRECT. ALSO, THE SECTIONS |
| | REFERENCED IN THE TABLE ARE NOT APPLICABLE- SECTION |
| | 503.4.1 PLASTIC PIPING- NOT APPLICABLE BECAUSE THE DUCT |
| | IS METAL. SECTION. 503.4.2 STATES- "SPECIAL GAS VENT |
| | SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL 1738 |
| | AND INSTALLED IN ACCORDANCE WITH THE SPECIAL GAS VENT |
| | MANUFACTURER'S INSTRUCTIONS"- NOT APPLICABLE BECAUSE |
| | THE EXHAUST SYSTEM IS NOT A UL 1738 LISTED AND LABELED |
| | SPECIAL GAS VENT. |
| | B) TYPE B VENTS SHALL BE LISTED IN ACCORDANCE WITH UL |
| | 441 PER SEC. 503.6.1 FBC FG. B VENTS ARE DOUBLE WALL- |
| | THE PLAN INDICATES AN UNLISTED SINGLE WALL GAS VENT IS |
| | BEING INSTALLED. PLEASE NOTE THAT TABLE 503.4 SPECIFIES |
| | B VENT TO BE USED ONLY FOR LISTED CATEGORY I |
| | APPLIANCES, LISTED APPLIANCES EQUIPPED WITH DRAFT HOOD, |
| | AND APPLIANCES LISTED FOR USE WITH TYPE B GAS VENT. |
| | NOTE #18 INDICATES THE ROASTERS ARE CATEGORY III |
| | APPLIANCES. |
| | |
| | 2) M2.0: IT APPEARS A NEW FRESH AIR DUCT AND A NEW |
| | IN-LINE EXHAUST FAN ARE TO BE CONNECTED TO THE COFFEE |
| | ROASTER'S 18-INCH MAIN EXHAUST DUCT. A) PROVIDE AN |
| | EQUIPMENT SCHEDULE FOR THE FAN AND A PRODUCT SUBMITTAL- |
| | SEC. 305.1 FBC FG. B) PROVIDE A SEQUENCE OF OPERATION |
| | FOR THE FAN- SEC. 503.3 & 503.6 FBC FG. C) REFER TO |
| | COMMENT #1 ABOVE AND PROVIDE EVIDENCE THAT INSTALLATION |
| | OF THE FAN IS CONSISTENT WITH THE MANUFACTURER'S |
| | SPECIFICATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |