| Plan Review Notes For Permit 22010840 |
| Permit Number |
22010840 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-08 17:43:45 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22010840 | | | 2/25/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE BUILDING OFFICIAL ROBERT BROWN HAS REVIEWED THE | | | LETTER FROM THE EOR- BRUCE M. CIARLARIELLO PE AND HAS | | | DETERMINED IT IS NOT A COMPLETE RATIONAL ANALYSIS FOR | | | THE COFFEE ROASTER EXHAUST/VENT SYSTEM AS WAS AGREED TO | | | BE PROVIDED BY THE EOR AT THE SITE MEETING. MR. BROWN | | | HAS MADE A SECOND REQUEST IN AN EMAIL TO MR. | | | CIARLARIELLO FOR THE COMPLETE RATIONAL ANALYSIS, AND | | | ALSO FOR A SIGNED COPY OF THE LETTER FROM RAY GARNER OF | | | NORDFAB DUCTING. PLEASE NOTE THAT FINAL GAS APPROVAL | | | FOR THE SYSTEM IS CONTINGENT ON APPROVAL OF THE | | | EXHAUST/VENT SYSTEM- SECS. 107.2.1 & 107.2.1.2 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|