Plan Review Notes
Plan Review Notes For Permit 22010834
Permit Number 22010834
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-05-16 10:42:53COMMENTS FROM PRIOR REVIEW NOT ADDRESSED.
  
 PLANS STATE BUILDING IS "FULLY SPRINKLERED" WITH FIRE
 ALARM SYSTEM. PLEASE ADDRESS FS AND FA SYSTEMS IN PLAN
 SET. SPECIFIY IF SYSTEMS ARE EXISTING OR NEW INSTALLS.
 IF NEW SYSTEM, PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 ALL WORK ON FIRE SPRINKLER OR ALARM SYSTEMS ARE
 REQUIRED TO BE COMPLETED BY A CERTIFIED CONTRACTOR AND
 SHALL COMPLY WITH NFPA STANDARDS. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 WORK ON THE SYSTEM. ALL SPRINKLER AND ALARM SYSTEM WORK
 MUST BE UNDER SEPARATE PERMITS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  
  