2022-05-17 12:43:58ELECTRIC REVIEW FAILED
 1) RESPONSE TO COMMENTS STATES A NOTE WAS ADDED TO
 SHEET E-0.01 STATING, GENERATOR, LOW VOLTAGE WIRING,
 FIRE ALARM SYSTEM, ACCESS CONTROL, SITE LIGHTING AND
 SIGNS ARE UNDER A SEPARATE PERMIT. PLEASE ADD THIS NOTE
 AS THIS NOTE CANNOT BE LOCATED ON SHEETS SUBMITTED .
 FBC 107.2
 2) PLEASE CORRECT RISER DIAGRAM TO DETAILTHE REQUIRED
 CONNECTION FOR TEMPORARY SOURCE OF POWER FOR
 MAINTAINANCE AND REPAIR OF THE ALTERNATE SOURCE OF
 POWER AS REQUIRED PER NEC 700.3(F) FOR EMERGENCY
 SYSTEMS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  