| 2022-05-17 12:43:58 | ELECTRIC REVIEW FAILED | | | 1) RESPONSE TO COMMENTS STATES A NOTE WAS ADDED TO | | | SHEET E-0.01 STATING, GENERATOR, LOW VOLTAGE WIRING, | | | FIRE ALARM SYSTEM, ACCESS CONTROL, SITE LIGHTING AND | | | SIGNS ARE UNDER A SEPARATE PERMIT. PLEASE ADD THIS NOTE | | | AS THIS NOTE CANNOT BE LOCATED ON SHEETS SUBMITTED . | | | FBC 107.2 | | | 2) PLEASE CORRECT RISER DIAGRAM TO DETAILTHE REQUIRED | | | CONNECTION FOR TEMPORARY SOURCE OF POWER FOR | | | MAINTAINANCE AND REPAIR OF THE ALTERNATE SOURCE OF | | | POWER AS REQUIRED PER NEC 700.3(F) FOR EMERGENCY | | | SYSTEMS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|