2022-03-16 15:10:41ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL CONDUIT LOCATIONS AND WIRING METHODS
 FOR FIRE PUMP FEEDERS TO ENSURE THEY COMPLY WITH NEC
 695.6
 2) PLEASE PROVIDE NOTES INSTRUCTING COMPLIANCE WITH
 DISCONNECT MARKING AS PER NEC 695.4(B)(3)(C)
 3) PLEASE PROVIDE DETAILS USED FOR INTEGRITY OF
 GENERATOR CONTROL WIRING TO COMPLY WITH NEC 695.14(F)
 4) PLEASE PROVIDE NOTE STATING FIRE PUMP GENERATOR
 OVERLOAD PROTECTION IS SHORT CIRCUIT ONLY, NO OVERLOAD
 PROTECTION
 5) PLEASE PROVIDE NOTES STATING, GENERATOR, LOW VOLTAGE
 WIRING, FIRE ALARM SYSTEM, ACCESS CONTROL, SITE
 LIGHTING AND SIGNS ARE UNDER A SEPARATE PERMIT
 6) PLEASE CHANGE NOMENCLATURE INDICATING DUCT HEATERS
 TO DEHUMIDIFIERS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved