Plan Review Notes
Plan Review Notes For Permit 22010834
Permit Number 22010834
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-11 09:13:19BUILDING ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ALL DRAWINGS NEED TO BE SIGNED BY THE DESIGNER OF
 THE DRAWING FBC WPB 107.1
  
 2) PLEASE SHOW THE RAMP LANDING DIMENSIONS AT THE TURN
 IN THE RAMP TO COMPLY WITH FBC ACCESSIBILITY
 405.7.4CHANGE IN DIRECTION.
 RAMPS THAT CHANGE DIRECTION BETWEEN RUNS AT LANDINGS
 SHALL HAVE A CLEAR LANDING 60 INCHES (1525 MM) MINIMUM
 BY 60 INCHES (1525 MM) MINIMUM.
  
 3) DRAWING S0.1 SHOWS THE DESIGN USE OF ASCE 7-10 -
 SHOULD BE ASCE 7-16 - PER FBC CHAPTER 35
  
 4) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE (18"
 BESIDE THE LATCH SIDE) TO EXIT THE ACCESSIBLE RESTROOM
 FBC ACCESSIBILITY 404.2.4
  
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS DOORS AND
 ROOFING SYSTEMS.