2022-03-18 11:26:431ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22010831
 3/18/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ME-1 SANITARY RISER: A) THE EXISTING LAV IS
 ALSO LABELED WC. B) THE TRAP ARM LENGTH FOR THE
 EXISTING LAV TO CONNECT TO THE VENT APPEARS TO BE
 EXCEEDING MAXIMUM DISTANCE OF 6 FT. FOR 1-1/2-INCH TRAP
 OR 5 FT. FOR 1-1/4- TABLE P3105.1 FBC RES. C) IT
 APPEARS THAT A HORIZONTAL WET VENT IS THE INTENTION FOR
 THE TWO BATHS HOWEVER IT IS NOT DRAWN IN COMPLIANCE
 WITH SECS. P3108.1-P3108.2.1 FBC RES.: EACH FIXTURE
 DRAIN SHALL CONNECT HORIZONTALLY, AND NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION. PLEASE CONNECT
 THE EXISTING LAV HORIZONTALLY TO THE 4-INCH DRAIN, AND
 RELOCATE THE DRY VENT TO THE UPPER LAV DRAIN OR BETWEEN
 THE TWO DRAINS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  