| 2022-03-18 11:26:43 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22010831 |
| | 3/18/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET ME-1 SANITARY RISER: A) THE EXISTING LAV IS |
| | ALSO LABELED WC. B) THE TRAP ARM LENGTH FOR THE |
| | EXISTING LAV TO CONNECT TO THE VENT APPEARS TO BE |
| | EXCEEDING MAXIMUM DISTANCE OF 6 FT. FOR 1-1/2-INCH TRAP |
| | OR 5 FT. FOR 1-1/4- TABLE P3105.1 FBC RES. C) IT |
| | APPEARS THAT A HORIZONTAL WET VENT IS THE INTENTION FOR |
| | THE TWO BATHS HOWEVER IT IS NOT DRAWN IN COMPLIANCE |
| | WITH SECS. P3108.1-P3108.2.1 FBC RES.: EACH FIXTURE |
| | DRAIN SHALL CONNECT HORIZONTALLY, AND NOT MORE THAN ONE |
| | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF |
| | THE DRY-VENTED FIXTURE DRAIN CONNECTION. PLEASE CONNECT |
| | THE EXISTING LAV HORIZONTALLY TO THE 4-INCH DRAIN, AND |
| | RELOCATE THE DRY VENT TO THE UPPER LAV DRAIN OR BETWEEN |
| | THE TWO DRAINS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |