| Plan Review Notes For Permit 22010813 |
| Permit Number |
22010813 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-26 10:14:37 | FIRE PROVISO: | | | | | | CARD READER INSTALLATIONS SHALL BE DONE | | | UNDER SEPARATE PERMIT & SHOP DRAWINGS | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|