2022-05-31 14:21:08ELECTRIC REVIEW FAILED
 1) IT APPEARS SPECIFICATIONS PROVIDED DO NOT INCLUDE
 THE TESLA BACKUP SWITCH. PLEASE PROVIDE THE
 SPECIFICATIONS FOR THIS SWITCH. FBC 107.2
 2) PLEASE DETAIL THE TESLA BACK UP SWITCH AS SERVICE
 ENTRANCE RATED TO COMPLY WITH NEC 230.66
 3) RESPONSE PROVIDED TO PREVIOUS COMMENTS STILL DO NOT
 ADDRESS WHETHER THE TESLA BACKUP SWITCH SHOULD NOT BE
 CONSIDERED THE FIRST MEANS OF DISCONNECT AS IS SHOWN ON
 THREE LINE DIAGRAM AND WOULD REQUIRE COMPLIANCE WITH
 NEC 230(A) (1)
 4) PLEASE DETAIL COMPLIANCE WITH NEC 250.24(A)(5) FOR
 200-AMP MAIN SERVICE PANEL AND AC DISCONNECT, EQUIPMENT
 GROUND AND GROUNDED CONDUCTORS ARE IN PARALLEL.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved