| 2022-05-31 14:21:08 | ELECTRIC REVIEW FAILED |
| | 1) IT APPEARS SPECIFICATIONS PROVIDED DO NOT INCLUDE |
| | THE TESLA BACKUP SWITCH. PLEASE PROVIDE THE |
| | SPECIFICATIONS FOR THIS SWITCH. FBC 107.2 |
| | 2) PLEASE DETAIL THE TESLA BACK UP SWITCH AS SERVICE |
| | ENTRANCE RATED TO COMPLY WITH NEC 230.66 |
| | 3) RESPONSE PROVIDED TO PREVIOUS COMMENTS STILL DO NOT |
| | ADDRESS WHETHER THE TESLA BACKUP SWITCH SHOULD NOT BE |
| | CONSIDERED THE FIRST MEANS OF DISCONNECT AS IS SHOWN ON |
| | THREE LINE DIAGRAM AND WOULD REQUIRE COMPLIANCE WITH |
| | NEC 230(A) (1) |
| | 4) PLEASE DETAIL COMPLIANCE WITH NEC 250.24(A)(5) FOR |
| | 200-AMP MAIN SERVICE PANEL AND AC DISCONNECT, EQUIPMENT |
| | GROUND AND GROUNDED CONDUCTORS ARE IN PARALLEL. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |