Plan Review Notes
Plan Review Notes For Permit 22010775
Permit Number 22010775
Review Stop E
Sequence Number 1
Notes
Date Text
2022-03-03 16:19:08ELECTRIC REVIEW FAILED
 1) PLEASE CLARIFY HOW THE TESLA BACK UP SWITCH SHOULD
 BE CLASSIFIED.IS THIS A SERVICE DISCONNECT?
 SPECIFICATIONS DETAIL A MAUNUAL SWITHC ON THE OUTSIDE
 OF THE HUB, HOWEVER, IT IS NOT SHOWN IN ANY SPECS. IS
 IT THE FIRST MEANS OF DISCONNECT? SHOULD NEUTRAL
 CONDUCTOR BE BONDED AT THIS LOCATION? DO NEUTRALS AND
 EQUIPMENT GROND CONDUCTORS NEED TO BE SEPERATED AT MAIN
 PANEL? PLEASE PROVIDE NEC CODE SECTIONS TO THAT PROVIDE
 NEC COMPLIANCE.
  
 CODES IN EFFECT NEC 215.5 AND FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  