| Plan Review Notes For Permit 22010767 |
| Permit Number |
22010767 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-07 14:06:50 | PRIVATE PROVIDER PLAN REVIEW AUDIT IS FAILED. | | | PLAN REVIEW AUDIT COMMENTS | | | | | | 1ST AUDIT: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WIND DESIGN DATA FOR THE WOOD FENCE IS | | | INCORRECT. THIS PROJECT IS UNDER THE 2020 FLORIDA | | | BUILDING CODE AND ASCE 7-16. THE FENCE IS A RISK | | | CATEGORY I WITH A VULT OF 150 MPH. THE EXPOSURE | | | CATEGORY IS C. PLEASE CORRECT THE WOOD FENCE | | | CALCULATIONS. FBC CITY AMENDMENTS SECTION 120 AND FBC | | | 1603.1.4 | | | | | | |
|