Plan Review Notes
Plan Review Notes For Permit 22010634
Permit Number 22010634
Review Stop B
Sequence Number 4
Notes
Date Text
2022-07-21 13:48:45BUILDING REVIEW APPROVED WITH PROVISO. (NOTE: PROVIDE
 INFORMATION FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1- PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE
 DRAINAGE DOESN'T AFFECT NEIGHBORS.
 2- SOFFIT CONSTRUCTION: PROVIDE SPECIFICATIONS FOR TYPE
 OF METAL PLASTER BASE FOR CEILINGS SHOWING COMPLIANCE
 WITH TABLE 3 OF ASTM C1063.
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED.
 B) OVERHEAD GARAGE DOOR MEETING THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT ON SHEET D-1.
 C) INSWING ENTRY DOOR AS SHOWN ON PLANS.
 D) NEW HORIZONTAL ROLLING WINDOW AS SHOWN ON PLANS.
 PLANS SHOW 2 PANEL WINDOW SIZE 111"X58".
 E) CLARIFY WHY SUBMITTING NOA FOR SINGLE HUNG WINDOWS.
 NOTE: IF REPLACING WINDOWS IN EXISTING BEDROOMS, THEN
 SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND
 TYPE OF PROPOSED WINDOW.
 4- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS.
 5- PROVIDE CURRENT ICYNENE ICC EVALUATION REPORT.
 (ARCHITECT TO APPROVE THE REPORT).
 6- REVISE ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME.
 B) DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 C) ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC. REVISE
 CALCULATIONS AS REQUIRED.
 D) WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A)
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH.
 E) ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND CROSS VENTILATION. REVISE AS REQUIRED OR PROVIDE
 COMPLETE INFORMATION SHOWING HOW COMPLYING WITH THESE
 CREDITS.
 F) HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED.
 G) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
 H) ATTIC AREA SPECIFIED ON PAGE 2 IS INCORRECT. SEE
 PLANS AND REVISE.
 I) DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
 J) WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 ALSO, CHECK MATERIAL OF SPECIFIED WINDOWS (VINYL OR
 METAL).
 NOTE: COORDINATE WITH ITEM #6(I).