Plan Review Notes
Plan Review Notes For Permit 22010634
Permit Number 22010634
Review Stop B
Sequence Number 3
Notes
Date Text
2022-07-15 17:49:18RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010634
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE:
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NOT ADDRESSED.
  
  
 3- OK.
 4- OK.
 5- OK.
 6- OK.
 7- OK.
  
 ORIGINAL COMMENT:
 8- WIND RESISTANCE OF EXTERIOR SOFFITS: ARCHITECT OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ONLY SPECIFIES STUCCO OVER
 PAPER BACKED METHAL LATHE. THERE ARE NO SPECIFICATIONS
 FOR WHAT KIND OF SHEATHING IS SUPPORTING THE METHAL
 LATH. ALSO, REVISE SIZE OF SPECIFIED FASCIA. SIZE
 SPECIFIED IS SMALLER THAN THE 2X10 JOISTS.
  
 PREVIOUS RESPONSE:
 THERE IS NOT INFORMATION PROVIDED FOR SOFFIT
 CONSTRUCTION. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE
 WITH ASTM C1063.
  
 RESPONSE TO CURRENT SUBMITTAL:
 REVISED TYPICAL WALL SECTION ON SHEET FD-1 ONLY
 SPECIFIES "METAL LATHE" AS THE METAL BASE TO SUPPORT
 THE STUCCO. THIS METAL BASE DOESN'T COMPLY WITH TABLE 3
 OF ASTM C1063 BASED ON THE CEILING RAFTERS SPACING. SEE
 TABLE 3 OF ASTM C1063 AND REVISE AS REQUIRED.
  
 9- OK.
  
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NO INFORMATION SUBMITTED.
 AND, NOT RESPONSE FROM CONTRACTOR IF SUBMITTING LATER A
 A DEFERRED SUBMITTAL.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)FROSTED GLASS GARAGE DOOR AS SPECIFIED ON PLANS.
  
 RESPONSE:
 DESIGN PRESSURES OF GARAGE DOOR ON FLORIDA PRODUCT
 APPROVAL FL16545-R13 SUBMITTED DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT ON SHEET D-1.
 NEED TO RESUBMIT. NEED PRODUCT APPROVAL OF GARAGE DOOR
 THAT MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES.
  
 ORIGINAL COMMENT:
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NO INFORMATION SUBMITTED.
 AND, NOT RESPONSE FROM CONTRACTOR IF SUBMITTING LATER
 AS A DEFERRED SUBMITTAL.
  
 E)OK.
  
 F)NEW HORIZONTAL ROLLING WINDOW.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. REVISED PLANS SHOW 2 PANEL
 WINDOW SIZE 111"X58". NOA 20-0813.06 SUBMITTED DOESN'T
 COVER THIS SIZE FOR 2 PANEL WINDOW. REVISE AS REQUIRED
 OR PROVIDE ANOTHER PRODUCT APPROVAL.
  
 NEW COMMENT:
 G)SINGLE HUNG WINDOWS: CLARIFY WHY SUBMITTING PRODUCT
 APPROVAL FOR SINGLE HUNG WINDOWS. PLANS DON'T SHOW ANY
 SINGLE HUNG WINDOWS. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: IF REPLACING WINDOWS IN EXISTING BEDROOMS, THEN
 SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND
 TYPE OF PROPOSED WINDOW.
  
 11-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 A) ICC EVALUATION REPORT ESR-2629 IS EXPIRED. THIS
 REPORT WAS SUBJECT TO RENEWAL ON 12/2019. NEED TO
 PROVIDE CURRENT REPORT.
  
 B) ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13-ENERGY CALCULATIONS SUBMITTED:
 A)OK.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 PARTIALLY DONE. STILL NEEDS OWNER'S NAME, BUILDER'S
 NAME.
  
 ORIGINAL COMMENT:
 C)DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D)OK.
  
 ORIGINAL COMMENT:
 F)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 G) OK.
  
 ORIGINAL COMMENT:
 H)WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A) FOR
 CONCRETE BLOCK WALL DOESN'T MATCH PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISED INFORMATION IS INCORRECT AGAIN. COORDINATE WITH
 ARCHITECT. SEE PLANS AND REVISE AS REQUIRED.
  
 I)OK.
  
 ORIGINAL COMMENT:
 J)ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND WHOLE HOUSE FAN. PLANS DON'T SHOW ANY OF THIS.
 REVISE AS REQUIRED OR PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE HOUSE IS COMPLYING WITH THESE CREDITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISED INFORMATION IS NOW IS TAKING CREDIT FOR CEILING
 FANS AND CROSS VENTILATION. PLANS DON'T SHOW ANY OF
 THIS. REVISE AS REQUIRED OR PROVIDE COMPLETE
 INFORMATION SHOWING HOW THE HOUSE IS COMPLYING WITH
 THESE CREDITS.
 NOTE: COORDINATE WITH ARCHITECT TO AVOID MORE
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 K)HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. PLANS SHOW TANKLESS WATER
 HEATER.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 L)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NO NAME PROVIDED. ONLY INITIALS WERE
 PROVIDED. NEED THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY THE CITED SECTION.
  
 M) OK.
  
 ORIGINAL COMMENT:
 N)ATTIC VENT INFORMATION ON PAGE 2 IS INCORRECT. REVISE
 AS REQUIRED. TYPICALLY, THE RATIO IS 1/150 NOT 1/300.
 SEC. R806.2 FBC-RESIDENTIAL. OR PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY DONE. THE ATTIC VENT RATIO WAS REVISED BUT
 THE ATTIC AREA WAS NOT. SEE PLANS FOR PITCHED ROOF
 AREAS AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 O)DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
  
 RESPONSE:
 REPEAT COMMENT. SEE NOTE ABOUT GLAZING IN DOORS AND
 REVISE AS REQUIRED. SEE PLANS AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 P)WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED
 WINDOWS (VINYL OR METAL).
  
 RESPONSE:
 COORDINATE WITH ITEM #13(O) ABOVE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]