| 2022-04-14 13:26:27 | 04/14/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. ON SHEET A-1, IT SHOWS A TANKLESS WATER HEATER; IS |
| | IT GAS OR ELECTRIC. WOULD YOU PLEASE CLARIFY PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 3. ON SHEET FD-1; |
| | |
| | A. DONE, BUT WITH A NEW COMMENT; THE SANITARY ISOMETRIC |
| | DIAGRAM IS HARD TO READ AS IT DOES NOT MATCH THE FLOOR |
| | PLAN. WOULD YOU PLEASE CORRECT TO MATCH PLANS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL PLUMBING? |
| | |
| | THE WASHING MACHINE IS NOT VENTED CORRECTLY PER THE |
| | 2020 FBC SEC. P 3101.2 TRAP SEAL PROTECTION. |
| | |
| | THE LAV IN THE IS NOT VENTED CORRECTLY PER THE 2020 FBC |
| | SEC. P 3101.2 TRAP SEAL PROTECTION. |
| | |
| | THE ISOMETRIC DOES NOT MATCH THE LAYOUT OF THE PLUMBING |
| | FIXTURE. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. SECOND REQUEST; IT DOES NOT SHOW THE WASHING |
| | MACHINE, BAR, OR KITCHEN SINK. WOULD YOU PLEASE SHOW |
| | AND LABEL PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENT? |
| | |
| | C. DONE. |
| | |
| | D. SECOND REQUEST; WOULD YOU PLEASE SHOW THE SOURCE OF |
| | HOT AND PROVIDE AN ISOMERIC WATER DIAGRAM PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| | PLUMBING. |
| | |
| | E. DONE. |
| | |
| | F. DONE. |
| | |
| | 4. ON SHEET A-1 AND ALL THAT APPLY, WOULD YOU PLEASE |
| | LABEL THE BATHROOMS. WOULD YOU PLEASE PROVIDE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 5. FORM R405-2020 SAYS AN ELECTRICAL HEATER, BUT GAS IS |
| | SHOWN ON PLANS. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 6. ON SHEET M-1, THE PLANS SHOW A DIFFERENT LAYOUT IN |
| | THE MASTER AREA IN COMPARICINE TO E-1 AND FD-1. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |