2022-05-17 18:13:26RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010634
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE:
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- DESIGN CRITERIA INFORMATION ON SHEET D-1. SPECIFIED
 ROOF DESIGN PRESSURES ARE NOT THE WORST CASE SCENARIO.
 SEE TABLE R301.2(2) AND TABLE R301.2(3)FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
 NOTE: NEED TO PROVIDE DESIGN PRESSURES FOR FLAT ROOF
 AND FOR PITCHED ROOF.
  
 RESPONSE:
 COMPONENTS AND CLADDING ROOF PRESSURES ARE INCORRECT.
 SEE TABLE R301.2(2) AND TABLE R301.2(3)FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 4- PROPOSED FLOOR PLAN SHOWS ONE WINDOW OF EXISTING
 BEDROOM #4 TO BE BLOCKED TO ALLOW FOR THE GARAGE
 ADDITION. SPECIFY SIZE AND TYPE OF EXISTING WINDOWS IN
 THIS BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- OK.
 6- OK.
 7- OK.
  
 ORIGINAL COMMENT:
 8- WIND RESISTANCE OF EXTERIOR SOFFITS: ARCHITECT OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ONLY SPECIFIES STUCCO OVER
 PAPER BACKED METHAL LATHE. THERE ARE NO SPECIFICATIONS
 FOR WHAT KIND OF SHEATHING IS SUPPORTING THE METHAL
 LATH. ALSO, REVISE SIZE OF SPECIFIED FASCIA. SIZE
 SPECIFIED IS SMALLER THAN THE 2X10 JOISTS.
  
 RESPONSE:
 THERE IS NOT INFORMATION PROVIDED FOR SOFFIT
 CONSTRUCTION. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE
 WITH ASTM C1063.
  
 9- OK.
  
 ORIGINAL COMMENT:
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 B)SLIDING GLASS DOORS.
  
 RESPONSE:
 INFORMATION SUBMITTED IS INCOMPLETE. ONLY THE DOOR
 DRAWINGS WERE SUBMITTED. IF THIS A FLORIDA PRODUCT
 APPROVAL , THEN NEED TO PROVIDE COMPLETE PRODUCT
 APPROVAL PACKAGE, INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS
 SUBMITTED. IF DOOR DOESN'T HAVE A FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA, THEN DOOR MANUFACTURER MAY
 SUBMIT COMPLETE ENGINEERING PACKAGE FOR REVIEW FOR
 LOCAL PRODUCT APPROVAL.
 NOTE: PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 C)FROSTED GLASS GARAGE DOOR AS SPECIFIED ON PLANS.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 E)OK.
  
 F)NEW HORIZONTAL ROLLING WINDOW.
  
 RESPONSE:
 REVISED PLANS SHOW 2 PANEL WINDOW SIZE 111"X58". NOA
 20-0813.06 SUBMITTED DOESN'T COVER THIS SIZE FOR 2
 PANEL WINDOW. REVISE AS REQUIRED OR PROVIDE ANOTHER
 PRODUCT APPROVAL.
  
 11-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 ORIGINAL COMMENT. ENERGY CALCULATIONS WERE NOT REVISED.
 ALL THE COMMENTS APPLY.
 13-ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)NUMBER OF BEDROOMS IS INCORRECT. SEE PLANS AND REVISE
 AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA DOESN'T MATCH PLANS. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A) FOR
 CONCRETE BLOCK WALL DOESN'T MATCH PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)CEILING INSULATION R-VALUE SPECIFIED ON ITEM #11(A)
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND WHOLE HOUSE FAN. PLANS DON'T SHOW ANY OF THIS.
 REVISE AS REQUIRED OR PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE HOUSE IS COMPLYING WITH THESE CREDITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. PLANS SHOW TANKLESS WATER
 HEATER. ALSO, CHECK WITH ARCHITECT IF GAS OR ELECTRIC.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 KL)PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 L) NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER
 "SPACES" IS INCORRECT. COORDINATE WITH NUMBER OF
 BEDROOMS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)ATTIC VENT INFORMATION ON PAGE 2 IS INCORRECT. REVISE
 AS REQUIRED. TYPICALLY, THE RATIO IS 1/150 NOT 1/300.
 SEC. R806.2 FBC-RESIDENTIAL. OR PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. FBC-RESIDENTIAL.
  
 N)DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
  
 O)WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED
 WINDOWS (VINYL OR METAL).
  
 P)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]