Plan Review Notes
Plan Review Notes For Permit 22010634
Permit Number 22010634
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-31 12:53:3101/31/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON SHEET A-1, IT SHOWS A TANKLESS WATER HEATER, IS
 IT GAS OR ELECTRIC. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET FD-1;
  
 A. THE SANITARY ISOMETRIC DIAGRAM IS HARD TO READ AS IT
 DOES NOT MATCH THE FLOOR PLAN. WOULD YOU PLEASE CORRECT
 TO MATCH PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING?
  
 B. I DOES NOT SHOW THE WASHING MACHINE, BAR, OR KITCHEN
 SINK. WOULD YOU PLEASE SHOW AND LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENT?
  
 C. TO MANY LAVS, THEY SHOW DOUBLES IN THREE LOCATIONS,
 BUT NONE ARE ON THE FLAT DRAWING. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW THE SOURCE OF HOT AND PROVIDE
 AN ISOMERIC WATER DIAGRAM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 E. THE CONNECTION ON THE BRANCHES IS IN THE WRONG
 DIRECTION PER THE 202 FBC SEC. R 3005.1 DRAINAGE
 FITTINGS AND CONNECTIONS.
  
 F. THERE IS A DOUBLE LAV THAT HAS NO VENT FOR IT. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  