| 2022-01-31 12:53:31 | 01/31/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. ON SHEET A-1, IT SHOWS A TANKLESS WATER HEATER, IS |
| | IT GAS OR ELECTRIC. WOULD YOU PLEASE CLARIFY PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 3. ON SHEET FD-1; |
| | |
| | A. THE SANITARY ISOMETRIC DIAGRAM IS HARD TO READ AS IT |
| | DOES NOT MATCH THE FLOOR PLAN. WOULD YOU PLEASE CORRECT |
| | TO MATCH PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.3.5.3 (12) RESIDENTIAL PLUMBING? |
| | |
| | B. I DOES NOT SHOW THE WASHING MACHINE, BAR, OR KITCHEN |
| | SINK. WOULD YOU PLEASE SHOW AND LABEL PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENT? |
| | |
| | C. TO MANY LAVS, THEY SHOW DOUBLES IN THREE LOCATIONS, |
| | BUT NONE ARE ON THE FLAT DRAWING. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. WOULD YOU PLEASE SHOW THE SOURCE OF HOT AND PROVIDE |
| | AN ISOMERIC WATER DIAGRAM PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| | |
| | E. THE CONNECTION ON THE BRANCHES IS IN THE WRONG |
| | DIRECTION PER THE 202 FBC SEC. R 3005.1 DRAINAGE |
| | FITTINGS AND CONNECTIONS. |
| | |
| | F. THERE IS A DOUBLE LAV THAT HAS NO VENT FOR IT. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |