Plan Review Notes
Plan Review Notes For Permit 22010634
Permit Number 22010634
Review Stop M
Sequence Number 1
Notes
Date Text
2022-02-09 10:15:471ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010634
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE RANGE. IS
 THERE GOING TO BE A HOOD ABOVE THE RANGE? HOW WILL IT
 COMPLY WITH THE MAKE UP REQUIREMENTS OF FBC RES M1503.4
  
 2) PLEASE SHOW THE RETURN AIR PATH BACK TO THE AHU, ARE
 THE DOORS OF THE AHU CLOSET LOUVERED? FBC RES M1602.3
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM THE MASTER
 SUITE BACK TO THE AHU. FBC RES M1602.3
  
 4) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL, SIZE
 AND TERMINATION LOCATION. FBC RES M1506.3
  
 5) PLEASE SHOW THE BATHROOMS EXHAUST TERMINATIONS
 LOCATIONS. FBC RES M1506.3
  
 6) PLEASE SHOW THE CONDENSING UNIT LOCATION. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  