| Plan Review Notes For Permit 22010634 |
| Permit Number |
22010634 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-09 10:15:47 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22010634 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE SPECIFICATIONS FOR THE RANGE. IS | | | THERE GOING TO BE A HOOD ABOVE THE RANGE? HOW WILL IT | | | COMPLY WITH THE MAKE UP REQUIREMENTS OF FBC RES M1503.4 | | | | | | 2) PLEASE SHOW THE RETURN AIR PATH BACK TO THE AHU, ARE | | | THE DOORS OF THE AHU CLOSET LOUVERED? FBC RES M1602.3 | | | | | | 3) PLEASE SHOW THE RETURN AIR PATH FROM THE MASTER | | | SUITE BACK TO THE AHU. FBC RES M1602.3 | | | | | | 4) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL, SIZE | | | AND TERMINATION LOCATION. FBC RES M1506.3 | | | | | | 5) PLEASE SHOW THE BATHROOMS EXHAUST TERMINATIONS | | | LOCATIONS. FBC RES M1506.3 | | | | | | 6) PLEASE SHOW THE CONDENSING UNIT LOCATION. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|