Plan Review Notes
Plan Review Notes For Permit 22010634
Permit Number 22010634
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-23 10:39:44RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010634
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- PROVIDE SITE PLAN SHOWING THE PROPOSED ADDITIONS AND
 SETBACKS AS REQUIRED BY SEC. 107.2.5 CITY AMENDMENTS.
 NOTE: BOUNDARY LINE SURVEY SHALL BE INCLUDED ALSO.
  
 2- LOT DRAINAGE:
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 3- DESIGN CRITERIA INFORMATION ON SHEET D-1. SPECIFIED
 ROOF DESIGN PRESSURES ARE NOT THE WORST CASE SCENARIO.
 SEE TABLE R301.2(2) AND TABLE R301.2(3)FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
 NOTE: NEED TO PROVIDE DESIGN PRESSURES FOR FLAT ROOF
 AND FOR PITCHED ROOF.
  
 4- PROPOSED FLOOR PLAN SHOWS ONE WINDOW OF EXISTING
 BEDROOM #4 TO BE BLOCKED TO ALLOW FOR THE GARAGE
 ADDITION. SPECIFY SIZE AND TYPE OF EXISTING WINDOWS IN
 THIS BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
  
 5- SHEET A-3:
 A)ROOF PLAN DOESN'T SPECIFY BEAMS FOR NEW ENTRY PORCH.
 PROVIDE BEAM TYPE, SIZE AND STRUCTURAL CONNECTORS. SEC.
 R301.2.1 FBC RESIDENTIAL.
  
 B)SPECIFY HOW THE NEW 2X10 ROOF JOISTS IN THE KITCHEN
 AREA ARE GOING TO BE FASTENED TO THE EXISTING BEAM.
 SEC. R301.2.1 FBC RESIDENTIAL.
 NOTE: ALSO, SPECIFY CONNECTION TO THE NEW (2)11-3/4"
 LVL BEAM
  
 C) SPECIFY CONNECTORS AT EACH END OF NEW (2)11-3/4" LVL
 BEAM LOCATED BETWEEN GREAT ROOM AND LIVING ROOM. SEC.
 R301.2.1 FBC RESIDENTIAL.
  
 D)REVISE ROOF SHEATHING NAIL TYPE AND SPACING SPECIFIED
 ON THE ROOF EDGE DETAIL. NEED TO USE RING SHANK NAILS
 AND ROOF SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES
 O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 E)ROOF EDGE DETAIL SUBMITTED IS ONLY FOR PITCHED ROOF.
 NEED TO PROVIDE ROOF EDGE DETAIL FOR FLAT ROOF ALSO.
 SEE FIGURE R301.2(7) FBC-RESIDENTIAL FOR FLAT ROOF
 DIAGRAM.
  
 F)BLOCK WALL EXTENSION DETAIL IN THIS DRAWING AND
 TYPICAL WALL SECTION ON DRAWING FD-1 SPECIFY FLAT ROOF
 ASSEMBLY WITH INSULATION (1" ISO INSULATION). SPECIFY
 THE R-VALUE OF THE INSULATION AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 6- DIMENSION PLAN ON SHEET A-2 DOESN'T SPECIFY THE
 WIDTH OF THE NEW HALLWAY
 LEADING FROM THE GARAGE TO THE LIVING ROOM. PROVIDE
 DIMENSION. SEC. R311.7.1 FBC-RESIDENTIAL.
  
 7- SPECIFY ROOF CROSS VENTILATION ON NEW ROOF AREAS AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY SIZE AND
 LOCATION.
  
 8- WIND RESISTANCE OF EXTERIOR SOFFITS: ARCHITECT OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ONLY SPECIFIES STUCCO OVER
 PAPER BACKED METHAL LATHE. THERE ARE NO SPECIFICATIONS
 FOR WHAT KIND OF SHEATHING IS SUPPORTING THE METHAL
 LATH. ALSO, REVISE SIZE OF SPECIFIED FASCIA. SIZE
 SPECIFIED IS SMALLER THAN THE 2X10 JOISTS.
  
 9- SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
 NOTE: THERE IS NO CARBON MONOXIDE ALARM SPECIFIED BY
 BEDROOM #4.
  
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)SLIDING GLASS DOORS.
  
 C)FROSTED GLASS GARAGE DOOR AS SPECIFIED ON PLANS.
  
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 E)FIXED WINDOW AS SHOWN ON PLANS.
  
 11-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13-ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)NUMBER OF BEDROOMS IS INCORRECT. SEE PLANS AND REVISE
 AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA DOESN'T MATCH PLANS. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A) FOR
 CONCRETE BLOCK WALL DOESN'T MATCH PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)CEILING INSULATION R-VALUE SPECIFIED ON ITEM #11(A)
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND WHOLE HOUSE FAN. PLANS DON'T SHOW ANY OF THIS.
 REVISE AS REQUIRED OR PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE HOUSE IS COMPLYING WITH THESE CREDITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. PLANS SHOW TANKLESS WATER
 HEATER. ALSO, CHECK WITH ARCHITECT IF GAS OR ELECTRIC.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 KL)PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 L) NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER
 "SPACES" IS INCORRECT. COORDINATE WITH NUMBER OF
 BEDROOMS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)ATTIC VENT INFORMATION ON PAGE 2 IS INCORRECT. REVISE
 AS REQUIRED. TYPICALLY, THE RATIO IS 1/150 NOT 1/300.
 SEC. R806.2 FBC-RESIDENTIAL. OR PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. FBC-RESIDENTIAL.
  
 N)DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
  
 O)WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED
 WINDOWS (VINYL OR METAL).
  
 P)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  