| 2022-04-19 10:21:25 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 220106121 |
| | 4/19/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET SP-4.01 GENERAL NOTES AND CONDITIONS: UPDATE |
| | ALL OUTDATED CODE REFERENCES AND COMPLIANCE STANDARDS |
| | INCLUDING THE APPLICABLE ANSI/APSP CONFORMANCE |
| | STANDARDS. STATE CLEARLY PRIVATE OR PUBLIC USE POOL- |
| | FBC B OR FBC RES- SEC. 107.2.1 WPB. |
| | |
| | 2) SP-401 & SP-403: SP-401 PUMP NOTE #10 INDICATES MAX |
| | FLOW NOT TO EXCEED 8 FPS IN RETURN, DESIGN VELOCITIES |
| | NOTE ON SP-4.03 INDICATES 10 FPS- PLEASE CORRECT. |
| | |
| | 3) SP-4.03 & SP-4.04: THE POOL PIPING PLAN SHOWS 2-INCH |
| | DRAIN PIPING, DUAL MAIN DRAIN DETAIL INDICATES |
| | 2-1/2-INCH PIPING. |
| | |
| | 4) SP-4.04: IDENTIFY ALL EQUIPMENT SHOWN IN THE |
| | ANCHORAGE DETAIL- SEC. 107.2.1 WPB. IT APPEARS THE |
| | FILTER IS NOT LABELED. |
| | |
| | 5) A-2.60 & SP.04 EQUIPMENT ROOM COMPLIANCES: CLARIFY |
| | HOW THE EQUIPMENT ROOM WILL BE VENTILATED AND IF A |
| | SHIP'S LADDER WILL BE INSTALLED FROM THE HATCH OPENING |
| | TO THE FLOOR- SEC. 454.1.5.4 FBC B. PLEASE NOTE THAT |
| | MINIMUM CEILING HEIGHT PER SEC. 454.1.5.6 IS 7-FT. |
| | |
| | 6) P-109: CLARIFY THE EXACT LOCATION OF THE BACKFLOW |
| | PREVENTER. PLEASE NOTE THAT THE DEVICE SHALL NOT BE |
| | INSTALLED IN CONFINED SPACE AND A MINIMUM OF 18-INCHES |
| | CLEARANCE SHALL BE PROVIDED ON ALL SIDES- SEC. H(5) WPB |
| | CROSS-CONNECTION MANUAL. A NOTE REQUIRING A SEPARATE |
| | PERMIT FOR THE BACKFLOW PREVENTER SHALL BE PLACED ON |
| | THE PLAN- SEC. 105.1 WPB. |
| | |
| | 7) SP.03 & SP.04: PROVIDE A MEANS OF DECHLORINATION FOR |
| | THE WASTE WATER DISCHARGING TO THE STORM SYSTEM- SEC. |
| | 90-205 (1) WPB CODE OR ORDINANCES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |