Plan Review Notes
Plan Review Notes For Permit 22010612
Permit Number 22010612
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-31 11:31:5812/17/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S
 MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED
 TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE
 PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE
 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER
 MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW
 RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF
 THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE
 TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM
 COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, AND FILTER. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, HEATER, FILTER, AND PUMP, PER THE WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
  
 4. A SEPARATE PERMIT IS REQUIRED FOR RPZ BACKFLOW
 DEVICE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 5. THE OVERFLOW CANNOT DISCHARGE TO THE SANITARY SYSTEM
 PER WPB CODE OF ORDINANCES CHAPTER 90, ART. III,
 SEC.90-126 (B) (5) UNLESS SPECIFICALLY AUTHORIZED BY
 THE CITY IN WRITING. PLEASE CONTACT THE CITY'S
 ENGINEERING DEPARTMENT AT 561-494-1085. THIS SECTION OF
 THE CODE PROHIBITS DISCHARGING POOL WATER TO THE
 SANITARY SEWER WITHOUT WRITTEN PERMISSION: HTTPS://LIBR
 ARY.MUNICODE.COM/FL/WEST_PALM_BEACH/CODES/CODE_OF_ORDIN
 ANCES?NODEID=PTIICOOR_CH90UT_ARTIIISESEDI_S90-126PRLIDI
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  