| 2022-07-29 11:13:46 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE ISOMETRIC |
| | LABELS THE SHOWER DRAIN AS WM. PLEASE CORRECT. |
| | |
| | 2. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE FLOOR PLAN |
| | ON P2 SHOWS A VENT FOR THE WATER CLOSET AND THE |
| | ISOMETRIC DOES NOT. PLEASE CORRECT. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - PAGE P3 - ON THE ISOMETRIC |
| | YOU'VE LABELED THE FIXTURE DRAIN FOR THE WATER CLOSET |
| | AS 2" AND 3" IS REQUIRED. |
| | |
| | 4. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE ISOMETRIC |
| | APPEARS TO BE MISSING THE WATER LINE FOR THE WATER |
| | CLOSET IN BATH 3. |
| | |
| | 5. 2020 FRC P2905.3 - ACCORDING TO THE SCALE ON YOUR |
| | WATER RISER, IT IS OVER 100 FEET FROM THE TANKLESS TO |
| | THE FARTHEST FIXTURE. IF THIS IS THE CASE, YOU WILL |
| | NEED A RECIRCULATING LINE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |