| 2022-08-01 11:32:32 | ELECTRIC REVIEW AUDIT FAILED |
| | 1) NEW PANELS AND ELECTRIC LOADS ARE DETAILED. PLEASE |
| | PROVIDE ACCURATE RISER DIAGRAM FOR ENTIRE SERVICE |
| | INCLUDING BOTH APARTMENTS AND GALLERY, INCLUDE |
| | CONDUCTOR AND OVERCURRENT SIZES. NEC 215.5 |
| | 2) PLEASE DETAIL COMPLIANCE WITH FBC R 315 REGARDING |
| | CARBON MONOXIDE ALARMS |
| | 3) PLEASE DETAIL WHAT DISCONNECT SHOWN ON FIRST FLOOR |
| | ELECTRIC PLAN IS USED FOR. FBC 107.2 |
| | 4) PLEASE REMOVE NOTE ON 2ND FLOOR ELECTRIC PLAN |
| | STATING ONLY WORK THIS APARTMENT = EXTEND TRACK. FBC |
| | 107.2 |
| | 5) DETAIL ALL ELECTRIC WORK TO BE REMOVED IN DEMOLISHED |
| | WALLS. PLEASE INCLUDE ELECTRIC PANELS, RECEPTACLES, |
| | SWITCHES, AIR CONDITIONING EQUIPMENT AND ANY OTHER |
| | APPLICABLE ELECTRIC WIRING |
| | 6) PLEASE SHOW COMPLIANCE FOR NEW ELECTRIC PANEL 427B |
| | FOR NEC 110.26 CLEARANCES. |
| | 7) ELECTRIC PANEL 427A APPEARS TO BE LOCATED IN A |
| | CLOSET WHICH IS NOT IN COMPLIANCE WITH NEC 240.24 (D) |
| | 8) PLEASE PROVIDE ALL DETAILS AND SPECIFICATIONS FOR |
| | NEW ELEVATOR, FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |