| Date |
Text |
| 2022-06-14 15:00:20 | FAILED |
| | |
| | 1) PROVIDE A SURVEY SHOWING ALL EASEMENTS AND SHOW ALL |
| | EASEMENTS AND FEATURES THAT ARE TO REMAIN AND CLEARLY |
| | SHOW THE SIGN AVOIDING THE EASEMENTS AND FEATURES. |
| | |
| | 2) THE SITE PLAN AND ENLARGED SITE PLAN SHOW THE SIGNS |
| | IN DIFFERENT LOCATIONS. |
| | |
| | 3) REPEAT COMMENT: THE ENLARGED SITE PLAN MONUMENT |
| | SHEET LISTS THE SETBACK FROM THE EDGE OF PAVEMENT AT 25 |
| | FEET, YET THE SIGN LOCATION AS DEPICTED SCALES AT 30 |
| | FEET FROM THE EDGE OF PAVEMENT. THE FOOTER FOR THE SIGN |
| | AT 25 FEET ENCROACHES INTO AN EASEMENT, WHILE THE SIGN |
| | AT 30 FEET AVOIDS THE 10-FOOT EASEMENT. NO PART OF THE |
| | SIGN MAY BE IN THE EASEMENT. PROVIDE ACCURATE, SCALED |
| | DIMENSIONS ON THE ENLARGED SITE PLAN MONUMENT SHEET |
| | VERIFYING THAT THE SIGN FOOTER DOES NOT ENCROACH THE |
| | EASEMENT. THE SETBACK FROM THE PROPERTY LINE MUST ALSO |
| | BE INCLUDED. NOTE: BASED ON THE SIZE/CONFIGURATION OF |
| | THE FOOTER SHOWN ON SHEET 06, A 10.9-FOOT SETBACK FROM |
| | THE PROPERTY LINE TO THE EDGE OF THE SIGN WILL KEEP THE |
| | SIGN FOOTER OUT OF THE EASEMENT. |
| | |
| | 4) REPEAT COMMENT: YOU NEED TO REVIEW THE NEW SIGN |
| | PLACEMENT AS IT APPEARS TO BE PLACED IN CONFLICT WITH A |
| | GROUP OF LARGE FPL TRANSFORMERS. STAFF HAS REVIEWED THE |
| | SIGN LOCATION THAT IS SHOWN ON THE CURRENT SITE PLAN |
| | AND IT APPEARS THAT THE TRANSFORMERS WILL BLOCK ONE |
| | SIDE OF THE SIGN. NOTE: THE EXISTING DRIVEWAY, WITH THE |
| | EXISTING MONUMENT SIGN, IS BEING REMOVED AND THE |
| | DRIVEWAY IS BEING REBUILT APPROXIMATELY 130 FEET TO THE |
| | SOUTH ALONG WEST EXECUTIVE CENTER DRIVE, SO THE SURVEY |
| | PHOTOS OF THE PROPOSED SIGN ARE NOT ACCURATE. IT IS |
| | EVIDENT THAT THE DRIVEWAY RELOCATION HAS NOT BEEN |
| | FACTORED INTO THE SIGN PLACEMENT AND THAT VISIBILITY |
| | WILL BE AN ISSUE AT THE PROPOSED LOCATION. |
| | |
| | PROPOSED MONUMENT #1 (GAS PRICE SIGN) - 240 SF |
| | PROPOSED MONUMENT #2 (PERMIT 22010576) - 240 SF |
| | TOTAL PROPOSED - 480 SF |
| | TOTAL PERMITTED - 988.2 SF |
| | |
| | NOTE: THE LANDSCAPE SHEET HAS BEEN REMOVED FROM THIS |
| | PERMIT APPLICATION. THE LANDSCAPE PLAN FOR THE BASE OF |
| | THE SIGN NEEDS TO BE SUBMITTED AS A LANDSCAPE PERMIT ON |
| | A PLAN SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | LANDSCAPE ARCHITECT. THE LANDSCAPE PLAN FOR THE SIGN |
| | MAY BE INCLUDED WITH THE OVERALL SITE LANDSCAPE PERMIT |
| | LANDSCAPE PLAN. |
| | |