2022-03-15 14:41:40WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22010567
 ADD: 1501 PRESIDENTIAL WAY # 3B
 CONT: PETRA BUILDERS GROUP
 TEL: 561-933-1818
 EMAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 02/2022
 ACTION: DENIED
  
 1) 2ND REQUEST. 1PLEASE REVIEW IN THE 2020 FBC-BUILDING
 CODE TABLE 1004.5 WHERE YOU SEE OUTPATIENT AREAS IS
 UNDER THE HEADING OF INSTITUTIONAL AREAS, THIS IS NOT A
 OUTPATIENT AREA WITHIN A INSTITUTION IS IT? MY GEO NAV
 INDICATES THE BUILDING IS A SINGLE STORY OFFICE COMPLEX
 AND BUSINESS OCCUPANCY. THE 2020 FBC-BUILDING CODE THE
 OCCUPANT LOAD FACTOR IS 150. 920SF/150= 7 OCCUPANTS
 2020 FBC-BUILDING CODE TABLE 1004.5.
  
 1ST ROUND COMMENTS. THE TITLE SHEET T.1 SHOWS THE
 OCCUPANCY AS BUSINESS AND THE OCCUPANT LOAD FACTOR AS
 100. PLEASE BE AWARE UNDER THE 2020 FBC-BUILDING CODE
 THE OCCUPANT LOAD FACTOR IS 150. 920SF/150= 7 OCCUPANTS
 2020 FBC-BUILDING CODE TABLE 1004.5.
  
 2) SHEET A.1:
 2A-D) COMPLIED.
  
  
 2E)2ND REQUEST. THE RESPONSE LETTER STATED SPACES AND
 ELEMENTS WITHIN EMPLOYEE WORK AREAS SHALL ONLY BE
 REQUIRED TO COMPLY WITH:
 206.2.8 HAS TO DEAL WITH 402 DEALS WITH A COMMON US
 CIRCULATION PATH AN ACCESSIBLE ROUTE. NOT SECTION 308
 AND 309.
 207.1. IS ABOUT AN ACCESSIBLE MEANS OF EGRESS (ENTRY) ,
 IT DOES NOT EITHER DEAL WITH SECTION 308 NOR 309.
 215.3 DEALS WITH AUDIBLE ALARM COVERAGE AT EMPLOYEE
 WORK AREAS, AGAIN NO CORRELATION WITH THE REQUIREMENTS
 FOUND IN 308 & 309.
 THE SCOPING REQUIREMENT FOUND IN THE 2020
 FBC-ACCESSIBILITY CODE SECTION 205.1 REQUIRES THE UNIT
 TO BE PLACED ABOVE THE ALLOWABLE REACH RANGES FOUND
 UNDER 308 AND OPERABLE PARTS FOUND IN 309. NONE OF THE
 EXCEPTIONS APPLY.
  
 1ST ROUND OF COMMENTS. ROOM 107 STERILE SHOWS AN OPEN
 SPACE PULL OUT SHELF AND OUTLET BEHIND. THE BOTTOM OF
 THE SHELF IS AT A HEIGHT OF 5 FEET ABOVE A. F. F. THIS
 DOES NOT MEET THE REACH RANGES AND OPERABLE PARTS.
 SHEET A.5
 DETAIL 4.
 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 2F)(1) ROOM 109 LAB GIVE DETAIL 3 ON A.5 WITH THE
 COUNTERTOP HEIGHT OF 3FEET WITH A SINK ALSO IN IT.
 2020 ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2F)(2) 2ND REQUEST. AGAIN SECTION 203.9 EMPLOYEE WORK
 AREAS SHALL BE DESIGNED & CONSTRUCTED SO THAT
 INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER AND
 EXIT THE EMPLOYEE WORK AREA.
 1ST ROUND OF COMMENTS. 2020 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2G-2I) COMPLIED.
  
 3) SEMI -COMPLIED. RESTROOM 105 SHEET A.3 DOOR SCHEDULE
 DOES NOW STATE A MEANS OF LOCKING THE DOOR FOR PRIVACY
 WITH PRIVACY LOCK BUT THIS IS A POCKET DOOR PROVIDE THE
 LOCKING MECHANISM FOR A POCKET DOOR. 2020 FBC-BUILDING
 SECTION 2902.3.5 DOOR LOCKING.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  