| 2022-01-19 11:24:37 | 02/01/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW, |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A.1; |
| | |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE AND |
| | DIMENSIONS FOR THE SINKS THAT APPLY THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | B. IN THE RESTROOM, WOULD YOU PLEASE GIVE THE |
| | DIMENSIONS FOR THE WATER CLOSET, LAV, AND TURNING |
| | RADIUS PER THE 2020 FBC ACC SEC. 305 CLEAR FLOOR OR |
| | GROUND SPACE. |
| | |
| | 2. ON SHEET A.3; |
| | |
| | A. THE TOILET DISPENSER IS SHOWN AT 36 INCHES FROM THE |
| | BACK ON THE RESTROOM DIAGRAM, AND ON THE WATER CLOSET |
| | DIAGRAM, IT IS SHOWN 9 INCHES. THE 36 INCHES IS |
| | INCORRECT PER THE 2020 FBC ACC SEC. 604.7. |
| | |
| | B. THE WATER CLOSET SAYS 18 INCHES, AND THE WATER |
| | CLOSET CAN BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM |
| | FROM THE SIDE WALL PER THE 2020 FBC ACC. SEC. 604.2 |
| | LOCATION. |
| | |
| | 3. ON SHEET A.5, THERE ARE SINKS, BUT PLEASE PROVIDE |
| | THE DIMENSION FOR THOSE THAT NEED TO COMPLY WITH THE |
| | 2020 ACC FBC SECTION 606.3. |
| | |
| | 4. ON SHEET P.1 UNDER PLUMBING GENERAL NOTES 14 A TALKS |
| | ABOUT HOT WATER BUT NON SHOWN ON THE PLANS. THERE ARE |
| | TWO SINKS THAT REQUIRE HOT WATER PER THE 2020 FBC |
| | SECTION 607.1. |
| | |
| | 5. ON SHEET P.2, PLEASE PROVIDE TRAP PRIMER FOR FLOOR |
| | DRAIN AND EQUIPMENT PER THE 2020 FBC SEC. 1002.4.1 TRAP |
| | SEAL PROTECTION. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT. |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |