2022-02-02 14:52:55WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22010567
 ADD: 1501 PRESIDENTIAL WAY # 3B
 CONT: PETRA BUILDERS GROUP
 TEL: 561-933-1818
 EMAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 02/2022
 ACTION: DENIED
  
 1) THE TITLE SHEET T.1 SHOWS THE OCCUPANCY AS BUSINESS
 AND THE OCCUPANT LOAD FACTOR AS 100. PLEASE BE AWARE
 UNDER THE 2020 FBC-BUILDING CODE THE OCCUPANT LOAD
 FACTOR IS 150. 920SF/150= 7 OCCUPANTS 2020 FBC-BUILDING
 CODE TABLE 1004.5.
  
 2) SHEET A2.1:
 2A) NOTE # 4 INDICATES 12-INCH-WIDE COUNTER @ 36 INCHES
 A. F. F. 2020 ACCESS. CODE 904.3.3 CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2B) NOTE # 5 INDICATES 12-INCH-WIDE COUNTER @ 42 INCHES
 A. F. F. ) 902.3 HEIGHT. THE TOPS OF WORK SURFACES
 SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 2C) FOR BOTH COMMENTS 2A & 2B PLEASE PROVIDE THE CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A SIDE
 APPROACH OR 306 A FORWARD APPROACH SHALL BE PROVIDED,
 KNEE AND TOE CLEARANCE COMPLYING WITH 306.
  
 2D) PLEASE PROVIDE COMPLIANCE WITH ACCESS. CODE 304.2
 CLEAR FLOOR SPACE (CIRCLE OR T SHAPE) FOR TURNING FROM
 DOOR 101 TO HALL 112 TOWARDS TREATMENT ROOM 110.
  
 2E) ROOM 107 STERILE SHOWS AN OPEN SPACE PULL OUT SHELF
 AND OUTLET BEHIND. THE BOTTOM OF THE SHELF IS AT A
 HEIGHT OF 5 FEET ABOVE A. F. F. THIS DOES NOT MEET THE
 REACH RANGES AND OPERABLE PARTS. SHEET A.5 DETAIL 4.
 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
 2F)(1) ROOM 109 LAB GIVE DETAIL 3 ON A.5 WITH THE
 COUNTERTOP HEIGHT OF 3FEET WITH A SINK ALSO IN IT.
 2020 ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2F)(2) 2020 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2G) NOTE: SPRAY POLYISO OPEN CELL FOAM TO UNDERSIDE OF
 DECK, USE CERTIFIED CONTRACTOR FOR THIS APPLICATION.
 PLEASE PROVIDE HOW THE APPLICATOR IS TO GAIN ACCESS TO
 THE UNDERSIDE OF ROOF DECK. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. PLEASE SHOW COMPLIANCE WITH
 SECTION 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES 2020 FBC-B.
  
 2H) NOTE: SPRAY POLYISO OPEN CELL FOAM TO UNDERSIDE OF
 DECK PLEASE PROVIDE A ICC-ES EVALUATION REPORT OR
 EQUIVALENT REPORT. PLEASE PROVIDE COMPLIANCE WITH
 2603.4.1.6 PROTECTION REQUIRED AN IGNITION BARRIER AND
 SECTION 2603.4 THERMAL BARRIERS. ADDITIONAL
 REQUIREMENTS MAY BE REQUIRED ONCE REPORT IS SUBMITTED.
  
 2I) RESTROOM 105 SEE SHEET A.3 ROOM FINISH SCHEDULE.
 THE SCHEDULE INDICATES THE RESTROOM WALLS ARE TO HAVE A
 PAINT FINISH. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2I)(1) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2I)(2) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
  
 2I)(3) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS
 AND PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY
 WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2I)(4) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED
 AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND
 WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3J) RESTROOM 105 SHEET A.3 DOOR SCHEDULE DOES NOT STATE
 A MEANS OF LOCKING THE DOOR FOR PRIVACY IS REQUIRED.
 2020 FBC-BUILDING SECTION 2902.3.5 DOOR LOCKING.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  