| Plan Review Notes For Permit 22010542 |
| Permit Number |
22010542 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-27 14:38:50 | ROOFING REVIEW: | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | | | ORIGINAL COMMENT: | | | A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON | | | 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY | | | MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED | | | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | RESPONSE: | | | PARTIALLY ADDRESSED. NEW NOA 20-0518.02 WAS SUBMITTED | | | BUT APPROVED ASSEMBLY TO BE INSTALLED WAS NOT | | | IDENTIFIED. CLEARLY MARK APPROVED ASSEMBLY TO BE | | | INSTALLED AND PROVIDE SIGNED RAS 117 CALCULATIONS IF | | | THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES | | | FOR ALL ROOF ZONES. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|