Plan Review Notes
Plan Review Notes For Permit 22010542
Permit Number 22010542
Review Stop B
Sequence Number 2
Notes
Date Text
2022-06-27 14:33:19RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010542
  
 NOTE:
 APARTMENT ADDITION: SEC. 606 FBC-EXISTING BUILDING.
 SEC. 1101.1 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 MAIN HOUSE: LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING
 BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 GARAGE CONVERSION: CHANGE OF OCCUPANCY SEC. 605 AND
 SEC. 1001.2.1, SEC. 604 AND SEC. 901.2, SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW WORK SHALL COMPLY WITH
 THE MATERIALS AND METHODS REQUIREMENTS IN THE FLORIDA
 BUILDING CODE.
  
 1- OK.
 2- OK.
 3- OK.
  
 4-ADDITION AND GARAGE CONVERSION TO STUDIO COMMENTS:
  
 ORIGINAL COMMENT:
 A)ENTRY DOOR DOESN'T COMPLY WITH THE MINIMUM CLEAR
 WIDTH REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. REVISE
 AS REQUIRED.
  
 RESPONSE:
 DOOR SCHEDULE WAS NOT REVISED. DOOR SIZE 2'-7 1/4" WIDE
 DOOR DOESN'T PROVIDE THE MINIMUM REQUIRED CLEAR WIDTH
 OF 32". SEE SEC. R311.2 FBC-RESIDENTIAL FOR PROPER WAY
 OF MEASURING THE CLEAR WIDTH AND REVISE DOOR SIZE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 B)GUEST BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 RESPONSE:
 SINGLE HUNG WINDOW SIZE 4'-0" WIDE X 4'-11 1/2" HIGH
 DOESN'T SEEM TO COMPLY WITH THE REQUIRED 24" CLEAR
 OPENING HEIGHT. TYPICALLY, 4'-11 1/2" HIGH WINDOWS
 DON'T PROVIDE THE 24" CLEAR OPENING HEIGHT. REVISE SIZE
 AS REQUIRED OR PROVIDE MANUFACTURER'S CUT SHEETS
 SHOWING THAT SPECIFIED WINDOW SIZE PROVIDES 24" CLEAR
 OPENING HEIGHT.
  
 5-MAIN HOUSE COMMENTS:
  
 ORIGINAL COMMENT.
 A)BOTH BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 RESPONSE:
 SINGLE HUNG WINDOW SIZE 4'-0" WIDE X 5'-0" HIGH DOESN'T
 SEEM TO COMPLY WITH THE REQUIRED 24" CLEAR OPENING
 HEIGHT. TYPICALLY, 5'-0" HIGH WINDOWS DON'T PROVIDE THE
 24" CLEAR OPENING HEIGHT. REVISE SIZE AS REQUIRED OR
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT
 SPECIFIED WINDOW SIZE PROVIDES 24" CLEAR OPENING
 HEIGHT.
  
 ORIGINAL COMMENT:
 B)SPECIFY SIZE OF INTERIOR DOORS. NEED TO SHOW
 COMPLIANCE WITH BATHROOM MINIMUM CLEAR DOOR OPENING AS
 REQUIRED BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SIZES OF INTERIOR DOORS WAS NOT PROVIDED. UNABLE TO
 CHECK COMPLIANCE.
 NOTE: ONLY 2'-8" DOOR OR WIDER DOORS COMPLY TO PROVIDE
 THE REQUIRED CLEAR OPENING WHEN DOOR IS OPEN.
  
 6- OK.
 7- OK.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON
 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 PARTIALLY ADDRESSED. NEW NOA 20-0518.02 WAS SUBMITTED
 BUT APPROVED ASSEMBLY TO BE INSTALLED WAS NOT
 IDENTIFIED. CLEARLY MARK APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C)SHUTTERS: CLARIFY WHY SUBMITTING "ASTRO GUARD"
 FLEXIBLE WIND ABATEMENT SYSTEM. WHERE IS THIS SYSTEM
 GOING TO BE INSTALLED?. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 RESPONSE:
 NO CLARIFIED AND NO INSTALLATION SCHEDULE WAS PROVIDED
 (IF SHUTTERS WILL BE INSTALLED).
  
 ORIGINAL COMMENT:
 D)ROOF TILE SHOWN IN THE ADDITION.
 NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF
 SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF
 SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING
 ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE.
  
 RESPONSE:
 PARTIALLY COMPLIED. NEED TO CLEARLY MARK/SPECIFY
 ADHESIVE PADDY SIZE.
  
 E) OK.
  
 DEFERRED SUBMITTAL.
 F)SHUTTERS AS SHOWN ON ADDITION/STUDIO (BARN TYPE). AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 NOTE:
 PLEASE MAKE SURE PRODUCT APPROVALS UPLOADED TO
 PROJECTDOX HAVE THE CORRECT FILE NAME. FOR EXAMPLE
 THERE IS ONE NAMED CASEMENT WINDOW BUT THE DRAWINGS
 UPLOADED TO THIS FILE ARE FOR ALUMINUM FRENCH DOORS.
 REVISE AS REQUIRED. COORDINATE WITH PERMIT LIBRARIAN IF
 NECESSARY.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY
 SUBMITTED.
  
 10- OK. PER RESPONSE LETTER ENERGY CALCULATIONS WILL
 NOT BE SUBMITTED. HISTORIC CONTRIBUTING STRUCTURES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  