| 2022-06-27 14:33:19 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22010542 |
| | |
| | NOTE: |
| | APARTMENT ADDITION: SEC. 606 FBC-EXISTING BUILDING. |
| | SEC. 1101.1 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION |
| | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | NOTE: |
| | MAIN HOUSE: LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING |
| | BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | NOTE: |
| | GARAGE CONVERSION: CHANGE OF OCCUPANCY SEC. 605 AND |
| | SEC. 1001.2.1, SEC. 604 AND SEC. 901.2, SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW WORK SHALL COMPLY WITH |
| | THE MATERIALS AND METHODS REQUIREMENTS IN THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- OK. |
| | 2- OK. |
| | 3- OK. |
| | |
| | 4-ADDITION AND GARAGE CONVERSION TO STUDIO COMMENTS: |
| | |
| | ORIGINAL COMMENT: |
| | A)ENTRY DOOR DOESN'T COMPLY WITH THE MINIMUM CLEAR |
| | WIDTH REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. REVISE |
| | AS REQUIRED. |
| | |
| | RESPONSE: |
| | DOOR SCHEDULE WAS NOT REVISED. DOOR SIZE 2'-7 1/4" WIDE |
| | DOOR DOESN'T PROVIDE THE MINIMUM REQUIRED CLEAR WIDTH |
| | OF 32". SEE SEC. R311.2 FBC-RESIDENTIAL FOR PROPER WAY |
| | OF MEASURING THE CLEAR WIDTH AND REVISE DOOR SIZE AS |
| | REQUIRED. |
| | |
| | ORIGINAL COMMENT: |
| | B)GUEST BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE |
| | EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1 |
| | FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE |
| | IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED. |
| | CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR |
| | A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT |
| | MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED |
| | AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS. |
| | NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW |
| | SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE |
| | WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS. |
| | |
| | RESPONSE: |
| | SINGLE HUNG WINDOW SIZE 4'-0" WIDE X 4'-11 1/2" HIGH |
| | DOESN'T SEEM TO COMPLY WITH THE REQUIRED 24" CLEAR |
| | OPENING HEIGHT. TYPICALLY, 4'-11 1/2" HIGH WINDOWS |
| | DON'T PROVIDE THE 24" CLEAR OPENING HEIGHT. REVISE SIZE |
| | AS REQUIRED OR PROVIDE MANUFACTURER'S CUT SHEETS |
| | SHOWING THAT SPECIFIED WINDOW SIZE PROVIDES 24" CLEAR |
| | OPENING HEIGHT. |
| | |
| | 5-MAIN HOUSE COMMENTS: |
| | |
| | ORIGINAL COMMENT. |
| | A)BOTH BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE |
| | EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1 |
| | FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE |
| | IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED. |
| | CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR |
| | A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT |
| | MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED |
| | AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS. |
| | NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW |
| | SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE |
| | WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS. |
| | |
| | RESPONSE: |
| | SINGLE HUNG WINDOW SIZE 4'-0" WIDE X 5'-0" HIGH DOESN'T |
| | SEEM TO COMPLY WITH THE REQUIRED 24" CLEAR OPENING |
| | HEIGHT. TYPICALLY, 5'-0" HIGH WINDOWS DON'T PROVIDE THE |
| | 24" CLEAR OPENING HEIGHT. REVISE SIZE AS REQUIRED OR |
| | PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT |
| | SPECIFIED WINDOW SIZE PROVIDES 24" CLEAR OPENING |
| | HEIGHT. |
| | |
| | ORIGINAL COMMENT: |
| | B)SPECIFY SIZE OF INTERIOR DOORS. NEED TO SHOW |
| | COMPLIANCE WITH BATHROOM MINIMUM CLEAR DOOR OPENING AS |
| | REQUIRED BY SEC. R320.1.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | SIZES OF INTERIOR DOORS WAS NOT PROVIDED. UNABLE TO |
| | CHECK COMPLIANCE. |
| | NOTE: ONLY 2'-8" DOOR OR WIDER DOORS COMPLY TO PROVIDE |
| | THE REQUIRED CLEAR OPENING WHEN DOOR IS OPEN. |
| | |
| | 6- OK. |
| | 7- OK. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | ORIGINAL COMMENT: |
| | A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON |
| | 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY |
| | MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | PARTIALLY ADDRESSED. NEW NOA 20-0518.02 WAS SUBMITTED |
| | BUT APPROVED ASSEMBLY TO BE INSTALLED WAS NOT |
| | IDENTIFIED. CLEARLY MARK APPROVED ASSEMBLY TO BE |
| | INSTALLED AND PROVIDE SIGNED RAS 117 CALCULATIONS IF |
| | THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| | FOR ALL ROOF ZONES. |
| | |
| | B) OK. |
| | |
| | ORIGINAL COMMENT: |
| | C)SHUTTERS: CLARIFY WHY SUBMITTING "ASTRO GUARD" |
| | FLEXIBLE WIND ABATEMENT SYSTEM. WHERE IS THIS SYSTEM |
| | GOING TO BE INSTALLED?. AND, PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| | |
| | RESPONSE: |
| | NO CLARIFIED AND NO INSTALLATION SCHEDULE WAS PROVIDED |
| | (IF SHUTTERS WILL BE INSTALLED). |
| | |
| | ORIGINAL COMMENT: |
| | D)ROOF TILE SHOWN IN THE ADDITION. |
| | NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF |
| | SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF |
| | SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING |
| | ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE. |
| | |
| | RESPONSE: |
| | PARTIALLY COMPLIED. NEED TO CLEARLY MARK/SPECIFY |
| | ADHESIVE PADDY SIZE. |
| | |
| | E) OK. |
| | |
| | DEFERRED SUBMITTAL. |
| | F)SHUTTERS AS SHOWN ON ADDITION/STUDIO (BARN TYPE). AND |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | |
| | NOTE: |
| | PLEASE MAKE SURE PRODUCT APPROVALS UPLOADED TO |
| | PROJECTDOX HAVE THE CORRECT FILE NAME. FOR EXAMPLE |
| | THERE IS ONE NAMED CASEMENT WINDOW BUT THE DRAWINGS |
| | UPLOADED TO THIS FILE ARE FOR ALUMINUM FRENCH DOORS. |
| | REVISE AS REQUIRED. COORDINATE WITH PERMIT LIBRARIAN IF |
| | NECESSARY. |
| | |
| | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY |
| | SUBMITTED. |
| | |
| | 10- OK. PER RESPONSE LETTER ENERGY CALCULATIONS WILL |
| | NOT BE SUBMITTED. HISTORIC CONTRIBUTING STRUCTURES. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |