| 2022-03-22 14:31:17 | ROOFING REVIEW: |
| | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON |
| | 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY |
| | MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | B)ROOF TILE SHOWN IN THE ADDITION. |
| | NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF |
| | SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF |
| | SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING |
| | ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE. |
| | |
| | C)NEED FOAM ADHESIVE PRODUCT APPROVAL IF USING FOAM. |
| | SEE ROOF TILE NOA FOR LISTED FOAM. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY |
| | SUBMITTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |