| 2022-02-02 13:15:52 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22010542 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE FIELD STUDIO HOUSE WILL NEED SEPARATE PERMITS. |
| | PLEASE REFERENCE THE MASTER PERMIT NUMBER ON THE FIELD |
| | STUDIO HOUSE. |
| | |
| | 2) THE ENERGY CALCULATIONS SUBMITTED IS FOR THE FIELD |
| | STUDIO HOUSE. PLEASE SUBMIT THE ENERGY CALCULATIONS FOR |
| | THE MAIN HOUSE. FBC EC 101.5.1.1.2 |
| | |
| | 3) THE DRAWING SUBMITTED DOES NOT SHOW ANY DOORS. |
| | PLEASE SUBMIT A DRAWING THAT CLEARLY SHOWS DOOR, |
| | LOUVERED DOORS IF INSTALLED IN FRONT OF THE AHU?S AND |
| | THE RETURN AIR PATH BACK TO THE AHU?S. FBC 107.2.1 |
| | |
| | 4) PLEASE SHOW THE ANCHORAGE OF THE CONDENSING UNITS. |
| | FBC RES M1307.2 |
| | |
| | 5) PLEASE SHOW THE CONDENSATE DRAIN PIPING MATERIAL, |
| | SIZE AND TERMINATION LOCATION. FBC RES M1411.3 |
| | |
| | 6) PLEASE SHOW THE HOOD LOCATION EXHAUST DUCT, CFM?S OF |
| | THE HOOD EXHAUST AND THE TERMINATION LOCATION OF THE |
| | HOOD EXHAUST FOR BOTH STRUCTURES. FBC RES M1503.4 |
| | |
| | 7) PLEASE SHOW THE DRYER LOCATION AND THE EXHAUST DUCT |
| | TERMINATION LOCATION FOR BOTH STRUCTURES. FBC RES M1502 |
| | |
| | 8) MAIN HOUSE: PLEASE SHOW THE BATH EXHAUST FANS AND |
| | THE EXHAUST TERMINATION LOCATION. FBC RES M1507.4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |