2022-02-02 13:15:521ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010542
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FIELD STUDIO HOUSE WILL NEED SEPARATE PERMITS.
 PLEASE REFERENCE THE MASTER PERMIT NUMBER ON THE FIELD
 STUDIO HOUSE.
  
 2) THE ENERGY CALCULATIONS SUBMITTED IS FOR THE FIELD
 STUDIO HOUSE. PLEASE SUBMIT THE ENERGY CALCULATIONS FOR
 THE MAIN HOUSE. FBC EC 101.5.1.1.2
  
 3) THE DRAWING SUBMITTED DOES NOT SHOW ANY DOORS.
 PLEASE SUBMIT A DRAWING THAT CLEARLY SHOWS DOOR,
 LOUVERED DOORS IF INSTALLED IN FRONT OF THE AHU?S AND
 THE RETURN AIR PATH BACK TO THE AHU?S. FBC 107.2.1
  
 4) PLEASE SHOW THE ANCHORAGE OF THE CONDENSING UNITS.
 FBC RES M1307.2
  
 5) PLEASE SHOW THE CONDENSATE DRAIN PIPING MATERIAL,
 SIZE AND TERMINATION LOCATION. FBC RES M1411.3
  
 6) PLEASE SHOW THE HOOD LOCATION EXHAUST DUCT, CFM?S OF
 THE HOOD EXHAUST AND THE TERMINATION LOCATION OF THE
 HOOD EXHAUST FOR BOTH STRUCTURES. FBC RES M1503.4
  
 7) PLEASE SHOW THE DRYER LOCATION AND THE EXHAUST DUCT
 TERMINATION LOCATION FOR BOTH STRUCTURES. FBC RES M1502
  
 8) MAIN HOUSE: PLEASE SHOW THE BATH EXHAUST FANS AND
 THE EXHAUST TERMINATION LOCATION. FBC RES M1507.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  