| Plan Review Notes For Permit 22010542 |
| Permit Number |
22010542 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-07 15:17:22 | ELECTRIC PLANE REVIEW FAILED | | | 1) PLEASE INDICATE ALL ELECTRIC METER MAINS, ELECTRIC | | | PANELS ON ELECTRICAL DRAWINGS. FBC 107.2 | | | 2) PLEASE PROVIDE PANEL SCHEDULES AND LOAD | | | CALCULATIONS. FBC 107.2 NEC 215.5 | | | 3) PLEASE INDICATE AIR HANDLING AND CONDENSING UNITS | | | LOCATIONS AND THERE ASSOCIATED CONDUCTORS ON ELECTRICAL | | | PLANS | | | 4) IT APPEARS GUEST HOUSE WILL REQUIRE MORE THAN ONE | | | MULTI WIRE CIRCUIT. PLEASE INDICATE THAT GUEST HOUSE | | | HAS SUBPANEL FOR GUEST HOUSE LOADS. AS PER NEC 225.30. | | | . | | | IN ADDITION, SINCE THIS GUEST HOUSE APPEARS IT WILL | | | REQUIRE AN ELECTRIC SUB PANEL, INDICATE THE NECESSARY | | | GROUNDING ELECTRODE SYSTEM AS PER NEC 250.32 | | | 5) REVISE ELECTRICAL RISER DIAGRAM AS NECESSARY TO | | | COMPLY WITH THE ABOVE COMMENTS | | | 6) PLEASE CHANGE NOMENCLATURE FOR SMOKE DETECTORS TO | | | INDICATE NECESSARY COMBINATION SMOKE/ CARBON ALARMS AS | | | REQUIRED DUE TO GAS APPLIANCES PRESENT. | | | 7) RECEPTACLE SPACING IN SEVERAL AREAS APPEAR TO BE | | | INADEQUATE ACCORDING TO NEC 210.52 (A)-(I) | | | |
|