2022-02-07 15:17:22ELECTRIC PLANE REVIEW FAILED
 1) PLEASE INDICATE ALL ELECTRIC METER MAINS, ELECTRIC
 PANELS ON ELECTRICAL DRAWINGS. FBC 107.2
 2) PLEASE PROVIDE PANEL SCHEDULES AND LOAD
 CALCULATIONS. FBC 107.2 NEC 215.5
 3) PLEASE INDICATE AIR HANDLING AND CONDENSING UNITS
 LOCATIONS AND THERE ASSOCIATED CONDUCTORS ON ELECTRICAL
 PLANS
 4) IT APPEARS GUEST HOUSE WILL REQUIRE MORE THAN ONE
 MULTI WIRE CIRCUIT. PLEASE INDICATE THAT GUEST HOUSE
 HAS SUBPANEL FOR GUEST HOUSE LOADS. AS PER NEC 225.30.
 .
 IN ADDITION, SINCE THIS GUEST HOUSE APPEARS IT WILL
 REQUIRE AN ELECTRIC SUB PANEL, INDICATE THE NECESSARY
 GROUNDING ELECTRODE SYSTEM AS PER NEC 250.32
 5) REVISE ELECTRICAL RISER DIAGRAM AS NECESSARY TO
 COMPLY WITH THE ABOVE COMMENTS
 6) PLEASE CHANGE NOMENCLATURE FOR SMOKE DETECTORS TO
 INDICATE NECESSARY COMBINATION SMOKE/ CARBON ALARMS AS
 REQUIRED DUE TO GAS APPLIANCES PRESENT.
 7) RECEPTACLE SPACING IN SEVERAL AREAS APPEAR TO BE
 INADEQUATE ACCORDING TO NEC 210.52 (A)-(I)
  