Plan Review Notes
Plan Review Notes For Permit 22010542
Permit Number 22010542
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-22 14:27:15RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010542
  
 NOTE:
 APARTMENT ADDITION: SEC. 606 FBC-EXISTING BUILDING.
 SEC. 1101.1 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 MAIN HOUSE: LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING
 BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 GARAGE CONVERSION: CHANGE OF OCCUPANCY SEC. 605 AND
 SEC. 1001.2.1, SEC. 604 AND SEC. 901.2, SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW WORK SHALL COMPLY WITH
 THE MATERIALS AND METHODS REQUIREMENTS IN THE FLORIDA
 BUILDING CODE.
  
 1)SEPARATE PERMITS. THERE ARE TWO SEPARATE BUILDINGS IN
 THIS PROPERTY. A SEPARATE PERMIT APPLICATION AND
 SUB-PERMITS ARE REQUIRED FOR EACH BUILDING. PLEASE
 SUBMIT A SEPARATE PERMIT APPLICATION AND SUB-PERMITS
 FOR THE APARTMENT ADDITION/GARAGE CONVERSION TO STUDIO.
 SAME PLANS CAN BE USED. CLEARLY SPECIFY THE VALUATION
 FOR THE APARTMENT ADDITION/GARAGE CONVERSION AND THE
 VALUATION FOR THE MAIN HOUSE ALTERATION.
 NOTE: SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 2- LOT DRAINAGE. PROPOSED WORK AFFECTS THE LOT
 DRAINAGE. PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE
 DRAINAGE IS KEPT WITHIN THE LOT AND NOT DIVERTED TO
 ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 3- PROVIDE SURVEY SHOWING THE PROPOSED ADDITION AND
 SETBACKS. SEC. 107.2.5 CITY AMENDMENTS. SEC. 107.3.5.3
 CITY AMENDMENTS.
  
 4-ADDITION AND GARAGE CONVERSION TO STUDIO COMMENTS:
 A)ENTRY DOOR DOESN'T COMPLY WITH THE MINIMUM CLEAR
 WIDTH REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. REVISE
 AS REQUIRED.
  
 B)GUEST BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 C)ROOF SCUPPERS: SPECIFY SIZE OF NEW SCUPPERS AND
 PROVIDE COMPLETE INFORMATION OF OVERFLOW SCUPPERS
 (LOCATION AND SIZE) AS REQUIRED BY SEC. R903.4.1
 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND THERE ARE 3 DIFFERENT ROOF AREAS.
  
 D)ROOF PLAN: SPECIFY ROOF PITCH AS REQUIRED BY SEC.
 R905.11.1 SLOPE.
 MODIFIED BITUMEN MEMBRANE ROOFS SHALL HAVE A DESIGN
 SLOPE OF NOT LESS THAN ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE
  
 5-MAIN HOUSE COMMENTS:
 A)BOTH BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 B)SPECIFY SIZE OF INTERIOR DOORS. NEED TO SHOW
 COMPLIANCE WITH BATHROOM MINIMUM CLEAR DOOR OPENING AS
 REQUIRED BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 C) FOOTING SCHEDULE IS MISSING SPECIFICATIONS FOR NEW
 MF20.12 FOOTING SHOWN ON THE FOUNDATION PLAN. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 6- SHEET S-103:
 A)REVISE WIND LOAD SCHEDULE. SHOW NEW ROOF AREAS AS
 REQUIRED BY CURRENT 2020 CODE FIGURE R3101.2(7)
 FBC-RESIDENTIAL.
  
 B)REVISE DIAGRAMS SHOWN BELOW THE WIND LOAD SCHEDULE.
 SHOW NEW ROOF AREAS AS REQUIRED BY CURRENT 2020 CODE
 FIGURE R3101.2(7) FBC-RESIDENTIAL.
  
 C)REVISE CORNER DISTANCE "A" SHOWN BELOW THE WIND LOAD
 SCHEDULE. CORNER DISTANCE IS 4'-0" MIN. AS REQUIRED BY
 NOTE "A" OF CURRENT 2020 CODE FIGURE R3101.2(7)
 FBC-RESIDENTIAL.
  
 D)PLYWOOD SHEATHING NAILING SCHEDULE: REVISE ROOF
 SHEATHING NAILING TYPE, SIZE AND SPACING. NEED TO USE
 RING SHANK NAILS AND ROOF SHEATHING NEEDS TO BE NAILED
 WITH AT 4 INCHES O.C. IN THE FIELD AND EDGES AS
 REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1
 FBC-RESIDENTIAL. REVISE NAILING ON ROOF ZONES
 ACCORDINGLY. COORDINATE WITH COMMENT 6(A)ABOVE.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 E) CLARIFY WHY THE LOADS ON THE DESIGN LOAD SCHEDULE
 ARE HIGHER FOR THE GARAGE THAN THE LOADS SHOWN FOR THE
 MAIN HOUSE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 7- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAILS
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR/WINDOW FRAME.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON
 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)FOLDING DOOR AS SHOWN ON PLANS. NEED COMPLETE PRODUCT
 APPROVAL. NEED TO PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED.
  
 C)SHUTTERS: CLARIFY WHY SUBMITTING "ASTRO GUARD"
 FLEXIBLE WIND ABATEMENT SYSTEM. WHERE IS THIS SYSTEM
 GOING TO BE INSTALLED?. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 D)ROOF TILE SHOWN IN THE ADDITION.
 NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF
 SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF
 SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING
 ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE.
  
 E)NEED FOAM ADHESIVE PRODUCT APPROVAL IF USING FOAM.
 SEE ROOF TILE NOA FOR LISTED FOAM.
  
 F)SHUTTERS AS SHOWN ON ADDITION/STUDIO (BARN TYPE). AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY
 SUBMITTED.
  
 10- THIS HOUSE IS A CONTRIBUTING HISTORIC HOUSE. ENERGY
 CALCULATIONS ARE NOT REQUIRED. BUT IF APPLICANT WANTS
 THEM TO BE PART OF THE CONSTRUCTION DOCUMENTS, THEN
 REVISE THEM AS FOLLOWS (NOTE: COORDINATE WITH
 ARCHITECTURAL PLANS TO AVOID CONFLICTS/DELAYS):
  
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT AND JURISDICTION NUMBER
 (THIS JURISDICTION IS 604700). SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 D) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  