| Plan Review Notes For Permit 22010531 |
| Permit Number |
22010531 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-08 16:07:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) THIS PROJECT IS | | | PERMITTED UNDER THE 2017 FBC. | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THERE ARE NO SHOP DRAWING REVIEW STAMPS FROM THE | | | DESIGNER OF RECORD OR THE CONTRACTOR ON THE WINDOW SHOP | | | DRAWINGS OR THE CALCULATIONS FOR THE EXTERIOR GLAZING | | | SYSTEMS. YOU CAN MAKE A COPY OF THE COVERSHEET TO PUT | | | THE STAMPS ON SO THAT THE DIGITALLY SIGNED DOCUMENTS | | | ARE NOT CORRUPTED OR USE A TRANSMITTAL DOCUMENT THAT | | | LISTS THE SPECIFIC PAGES CONTAINED IN THE DOCUMENTS. | | | FBC AMENDMENTS 107.3.4 |
|