| Plan Review Notes For Permit 22010524 |
| Permit Number |
22010524 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-01 17:20:25 | MECHANICAL APPROVED WITH PRIVISO: | | | | | | 606.2 WHERE REQUIRED. SMOKE DETECTORS SHALL BE | | | INSTALLED | | | WHERE INDICATED IN SECTIONS 606.2.1 THROUGH 606.2.3. | | | 606.2.1 TO PREVENT THE RECIRCULATION OF DANGEROUS | | | QUANTITIES | | | OF SMOKE, A DETECTOR APPROVED FOR AIR DUCT USE SHALL BE | | | INSTALLED ON THE SUPPLY SIDE OF AIR-HANDLING SYSTEMS AS | | | REQUIRED BY NFPA 90A, STANDARD FOR THE INSTALLATION OF | | | AIR CONDITIONING AND VENTILATING SYSTEMS. SMOKE | | | DETECTORS | | | LISTED FOR USE IN AIR DISTRIBUTION SYSTEMS SHALL BE | | | LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY | | | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE | | | CAPACITY GREATER THAN 2000 CUBIC FEET PER MINUTE. |
|