Plan Review Notes
Plan Review Notes For Permit 22010487
Permit Number 22010487
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-01-19 14:16:53FIRE PROVISO:
  
 TEST @ 200PSI FOR 2 HOURS PER NFPA13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS
 CHARGED/DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL
 FOR LEAKS & INSPECTOR DRAIN AFTER 2 HRS)
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  