| 2022-01-19 14:16:53 | FIRE PROVISO: | | | | | | TEST @ 200PSI FOR 2 HOURS PER NFPA13 | | | | | | CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION | | | (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS | | | CHARGED/DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL | | | FOR LEAKS & INSPECTOR DRAIN AFTER 2 HRS) | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|