| 2022-02-03 11:17:46 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22010486 1400 CENTREPARK BLVD # 500 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. A-4/DETAIL 4: PER FBC ACC 603.3, MIRRORS LOCATED |
| | ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH |
| | THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER WPB FBC |
| | 107.2.1, PLEASE REVISE TO CLARIFY THE SAME. |
| | |
| | 2. A-4/DETAIL 1 AND 2: ACCESSIBLE URINALS SHALL BE THE |
| | STALL-TYPE OR THE WALL-HUNG TYPE WITH THE RIM 17 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC |
| | 605.2. PER WPB FBC 107.2.1, PROVIDE DETAIL. |
| | |
| | 3. PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. PER WPB FBC 107.2.1, PROVIDE NOTE. |
| | |
| | 4. A-2 AND A-11: PER WPB FBC 107.2.1, PROVIDE CLEAR |
| | FLOOR SPACE FOR SINK IN CAF? RM 512 COMPLYING WITH FBC |
| | ACC 305 POSITIONED FOR A FORWARD APPROACH AND CENTERED |
| | ON THE UNIT. |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE LOCATION OF DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH FBC PL 403.1, TABLE |
| | 403.1 AND 403.5. IF THERE ARE NONE, PROVIDE DRINKING |
| | FOUNTAIN(S) COMPLYING WITH FBC PL 410.3, FBC ACC 211.2 |
| | AND 602.1 THROUGH 602.6 AND 602.7. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE LOCATION OF SERVICE |
| | SINK SHOWING COMPLIANCE WITH FBC PL TABLE 403.1. |
| | |
| | 7. P0.1/PLUMBING FIXTURE SCHEDULE SPECIFIES NEW WALL |
| | HUNG WATER CLOSETS (TAG HWC); THE SANITARY RISER |
| | DIAGRAM INDICATES FLOOR MOUNTED. PER WPB FBC 107.2.1, |
| | CLEARLY SHOW ON THE RISER DIAGRAM THE CARRIER ASSEMBLY |
| | AND VENTING. RECONCILE P2.1 WITH REVISED RISER DIAGRAM. |
| | |
| | 8. P0.1 PLUMBING NOTES: |
| | ...A) NOTES 1, 11,24,25 ALL REFER TO 6TH EDITION FOR |
| | 2020 FLORIDA BUILDING CODES. PER WPB FBC 107.2.1, |
| | CORRECT TO STATE 7TH EDITION. |
| | ...B) NOTE 11 CALLS FOR TYPE L COPPER FOR WATER |
| | DISTRIBUTION PIPE BUT ALLOWS ALTERNATE MATERIALS. PRIOR |
| | TO INSPECTION, A PLAN REVISION REFLECTING THE ACTUAL |
| | MATERIAL SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT, |
| | APPROVED AND ON SITE. WPB FBC 107.2.1. |
| | ...C) NOTE 12 CALLS FOR CAST IRON OR PVC FOR THE |
| | SANITARY PIPING. PRIOR TO INSPECTION, A PLAN REVISION |
| | REFLECTING THE ACTUAL MATERIAL SHALL BE SUBMITTED TO |
| | THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB FBC |
| | 107.2.1. |
| | ...D) NOTE 24 CALLS FOR TYPE L COPPER WITH ARMAFLEX |
| | INSULATION FOR CONDENSATE PIPING THEN ALLOWS PVC WITH |
| | INSULATION IN RETURN AIR PLENUMS. PER WPB FBC 107.2.1, |
| | CLARIFY. ADDITIONALLY, PROVIDE THE FIRE/SMOKE RATING |
| | FOR THE INSULATION. PRIOR TO INSPECTION, A PLAN |
| | REVISION REFLECTING THE ACTUAL MATERIAL SHALL BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT, APPROVED AND ON |
| | SITE. WPB FBC 107.2.1. |
| | ...E) NOTES 26 AND 28: BOTH ALLOW USE OF AIR ADMITTANCE |
| | VALVES/STUDOR VENTS TO BE USED FOR VENT PIPING THROUGH |
| | THE ROOF. |
| | ......1) PLEASE NOTE; FBC PL 918.3.1 REQUIRES AIR |
| | ADMITTANCE VALVES ARE LOCATED MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. THE SCOPE OF WORK IS ON THE |
| | 5TH FLOOR OF A 10 STORY BUILDING. PER WPB FBC 107.2.1, |
| | CLARIFY. IS IT THE INTENT THAT ONE OF THE TWO NOTES |
| | ALLOW AIR ADMITTANCE VALVES/STUDOR VENTS FOR |
| | INDIVIDUAL/BRANCH VENTS? PRIOR TO INSPECTION, A PLAN |
| | REVISION REFLECTING ANY ACTUAL USE OF AIR ADMITTANCE |
| | VALVES/STUDOR VENTS SHALL BE SUBMITTED TO THE BUILDING |
| | DEPARTMENT, APPROVED AND ON SITE. WPB FBC 107.2.1. |
| | ...F) NOTE 33 SEEMS TO HAVE NO BEARING ON THE PROJECT. |
| | PER WPB FBC 107.2.1, IF THIS IS THE CASE, PLEASE DELETE |
| | IT. |
| | ...G) PER WPB FBC 107.2.1, PROVIDE NOTE STATING "ALL |
| | COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE LEAD |
| | FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1." |
| | |
| | 9. P0.1 WATER RISER: PER WPB FBC 107.2.1, PROVIDE |
| | SCHEMATIC DETAIL FOR THE DISHWASHER/SINK/ IWH TO |
| | INCLUDE VALVES AND WATER HAMMER ARRESTOR (SEE FBC PL |
| | 604.9). |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTER |
| | SCHEDULE AND SPECIFY BACKFLOW PREVENTER TYPE AND |
| | STANDARD (ASSE, ASME ETC.). PROVIDE NOTE, BACKFLOW |
| | PREVENTERS SHALL BE LEAD FREE. |
| | |
| | 11. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE |
| | DISHWASHER SHOWING COMPLIANCE WITH FBC PL 409.4. THE |
| | WASTE CONNECTION OF A RESIDENTIAL DISHWASHER SHALL |
| | CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE |
| | TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE |
| | DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR |
| | THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF |
| | A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY |
| | FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER |
| | TOP. |
| | |
| | 13. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| | WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING |
| | WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| | |
| | 14. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUALS FOR ANY EQUIPMENT |
| | REQUIRING A PLUMBING CONNECTION THAT IS NOT LISTED ON |
| | THE PLUMBING FIXTURE SCHEDULE. IF THESE MAY BE DEFERRED |
| | IN ACCORDANCE WITH WPB FBC 107.3.4.2 AS LONG AS THEY |
| | ARE LISTED ON THE PLANS. SAID DOCUMENTS SHALL BE |
| | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| | INSPECTION. |
| | |
| | 15. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE |
| | CONNECTION SCHEDULE; DFU/TRAP SIZE AND WSFU/CONNECTION |
| | SIZE |
| | |
| | 16. P2.1/FLOOR DRAIN FOR ICEMAKER |
| | ...A) WASTE RECEPTORS SHALL NOT BE INSTALLED IN |
| | CONCEALED SPACES. READY ACCESS SHALL BE PROVIDED TO |
| | WASTE RECEPTORS PER FBC PL 802.4. PER WPB FBC 107.2.1, |
| | SHOW COMPLIANCE. |
| | ...B) PER WPB FBC 107.2.1, PROVIDE DETAIL AND |
| | SPECIFICATION FOR TRAP PRIMER |
| | ...C) PER WPB FBC 107.2.1, PROVIDE DETAIL OF FLOOR |
| | DRAIN AND ICE MAKER DISCHARGE WITH AIR GAP |
| | |
| | 17. PER WPB FBC 107.2.1, PROVIDE AC CONDENSATE PIPE |
| | ROUTING AND SIZES. COMPLY WITH THE REQUIREMENTS OF FBC |
| | PL 314. |
| | |
| | 18. P0.1/WATER RISER: PER WPB FBC 107.2.1, CORRECTLY |
| | IDENTIFY SK-2. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |