Plan Review Notes
Plan Review Notes For Permit 22010462
Permit Number 22010462
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-02 10:19:1602/02/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON RE-REVIEWING SUBMITTED CORRECTIONS.
  
 1. ON SHEET A03;
  
 A. THE BREAK ROOM SINK, WOULD YOU PLEASE SHOW THE CLEAR
 FLOOR SPACE AND DIMENSIONS PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 B. IN THE SPA ROOM, THERE IS A SINK. WOULD YOU PLEASE
 SHOW THE CLEAR FLOOR SPACE AND DIMENSIONS PER THE 2020
 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 D. WOULD YOU PLEASE SHOW 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR-ACCESSIBLE
 DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE.
  
 E. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 F. FOR THE HAIR AND SPA ROOMS, WOULD YOU PLEASE SHOW
 WHICH ONE WILL COMPLY WITH THE 2020 FBC ACC PER THE
 SEC. 212.3 SINKS.
  
 2. ON SHEET A04;
  
 A. TOP RIGHT HAND, THERE IS A DRAWING SHOWING THE
 MIRROR AT 44 INCHES, AND IT SHOULD BE AT 40 INCHES PER
 THE 2020 FBC ACC SEC. 603.3.
  
 B. THE SECOND DRAWING DOWN FROM THE TOP RIGHT SHOWS
 GRAB BARS AND MIRRORS ON THE WRONG DIMENSION, WHICH
 LOOKS LIKE A DUPLICATE. THE SECOND DRAWING ON THE
 BOTTOM LEFT IS CORRECT. WOULD YOU REMOVE OR CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. THE TOILET GRAB BAR SAYS 6
 INCHES FROM THE WALL, WHICH IS NOT AN ACTUAL NUMBER AS
 THE TOILET IS 16 INCHES TO 18 INCHES TO THE CENTER,
 WHICH MAY CONFUSE THE INSTALLER. WOULD YOU PLEASE
 CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. THE DRAWING THAT SAYS BATHROOM CLEARANCES HAS THE
 LEFT ONE DETAIL INCORRECT FOR THE TOILET PAPER, LAV
 DISTANCE THAT DOES NOT COMPLY WITH THE 2020 FBC ACC.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR-ACCESSIBLE
 DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE.
  
 E. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 3. ON SHEET A05, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR LAV, DRINKING FOUNTAIN, AND SINKS FOR
 PREVIOUS COMMENTS PER THE SEATS OF WATER CLOSETS SHALL
 BE OPEN-FRONT TYPE PER 2020 FBC P 425.3 WATER CLOSET
 SEATS.
  
 4. ON SHEET P-1;
  
 A. THERE IS A GAS WATER HEATER, AND IT DOES NOT SHOW A
 DRAIN PAN, BUT A DRAIN PAN ON P04 DRAINING TO THE MOP
 SINK IS THE DRAIN BY GRAVITY TO THE MOP SINK. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE SHOW THE MAIN SHUT-OFF ON THIS AND
 P03 PER THE 2020 FBC SEC. P 606.1 (2) LOCATION OF
 FULL-OPEN VALVES.
  
 C. NEXT TO THE WATER HEATER, IT SHOWS A HOSE BIBB.
 WOULD YOU PLEASE LABEL IT, SHOW IT IN P03, AND SHOW A
 SHUT-OFF PER THE 2020 FBC SEC P 606.2 LOCATION OF
 SHUTOFF VALVES.
  
 D. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNIT AND WITHIN REACH PER
 THE 2020 FBC SEC. P 606.3 ACCESS TO VALVES.
  
 5. ON SHEET P-2;
  
 A. IT CALLS OUT A WASHING MACHINE THAT WILL REQUIRE A
 LINT TRAP. WOULD YOU PLEASE SUPPLY DETAILS OR NOTES PER
 THE 2020 FBC SEC. 1003.6.
  
 B. WOULD YOU PLEASE SHOW THE CLEANOUT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THE PC IS VENTED INCORRECTLY PER THE 2020 FBC SEC. P
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
  
 D. THE SPA LAV 101, 102, 109, 110 111, 112, 114, 115,
 117, 118, 126, 127, 128, 129, 130 AND 131 ARE NOT
 PEOPERLY VENTED PER THE 2020 FBC SEC. P 1002.1 FIXTURE
 TRAPS.
  
 6. ON SHEET P03, HOT WATER LINES LOOPED FOR THE
 RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE SEC.
 C404.6.1. THERE IS A TABLE THAT LIMITS THE BETWEEN THE
 SOURCE AND THE OUTLET; PLEASE REFER TO TABLE 404.5.1
 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 7. ON SHEEP P04;
  
 A. ON THE GAS HEATER DETAIL, THE BOTTOM-FED WATER
 HEATERS AND BOTTOM-FED TANKS CONNECTED TO WATER HEATERS
 SHALL HAVE A VACUUM RELIEF VALVE INSTALLED PER THE 2020
 FBC SEC. P 504.2VACUUM RELIEF VALVE.
  
 B. THE UNIT LOOKS LIKE IT IS ELEVATED. WILL IT BE ON A
 STAND OR IN BRACKETS ON THE WALL? WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? IF NOT ON STAN
 YOU, PLEASE PROVIDE A DETAIL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS.
 PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS FOR THE
 SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 D. UNDER GENERAL NOTES, IT SAYS #3 (D) INSULATION ON
 THE FIRST 8 FT, BUT THE RECIRCULATING SYSTEM THE PIPING
 SHALL BE INSULATED IN ITS ENTIRETY, INCLUDING THE
 SUPPLY AND RETURN PIPING OF A CIRCULATING PER C404.4
 (A) INSULATION OF PIPING.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE CORRECTION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY
 PAGES. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  