| 2022-02-07 09:51:22 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22010462 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) FROM THE DRAWINGS SUBMITTED IT APPEARS THAT THE 2 |
| | MASSAGE SPA AREAS ARE NOT ACCESSIBLE FROM THE MIZNER |
| | HAIR AND NAILS TENANT SPACE. THEY APPEAR TO BE SEPARATE |
| | TENANT SPACES AND WOULD NEED THEIR OWN MECHANICAL |
| | SYSTEMS. PLEASE SHOW HOW THESE 2 TENANT SPACES WILL |
| | HAVE ACCESS TO THE MECHANICAL SYSTEMS AND CONTROLS. FBC |
| | M 405.1 |
| | |
| | 2) THE BEAUTY SALON WILL REQUIRE 1969 CFM OF OUTDOOR |
| | AIR AND 1905 CFM?S OF EXHAUST AIR. PLEASE SHOW HOW THE |
| | EXHAUST AIR WILL BE REMOVED AS I DO NOT SEE ANYTHING ON |
| | THE EXHAUST FANS FOR THIS AMOUNT OF EXHAUST. FBC M |
| | TABLE 403.3.1.1 |
| | |
| | 3) PLEASE ADD DETAIL DRAWINGS OF THE PEDICURE AND |
| | MANICURE EXHAUST ALONG WITH THE TOTAL AMOUNT OF EXHAUST |
| | REQUIRED FOR EACH AND A DRAWING DETAIL OF THE EXHAUST |
| | SYSTEM FOR THESE. FBC M 502.20 |
| | |
| | 4) PLEASE REMOVE THE REFLECTIVE CEILING LAYER ON THE |
| | MECHANICAL DRAWINGS SO THE REVIEW IS MORE CLEAR TO THE |
| | REVIEWER. FBC 107.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |