| 2022-02-02 10:05:25 | 02/02/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW, |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON RE-REVIEWING SUBMITTED CORRECTIONS. |
| | |
| | 1. ON P04; |
| | |
| | A. THE BTU LOAD FOR THE WATER HEATER IS FOR A |
| | TANK-LESS, BUT THE PLAN SAYS AND SHOWS A TANK TYPE AND |
| | 199 BTU'S ARE MOST TANK-LESS AND TANK TYPE ARE ABOUT 50 |
| | BYU'S. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE SUBMIT MANUFACTURES SPECIFICATIONS |
| | FOR THE DRYER AND TANK-LESS TO VERIFY COMPLIANCE WITH |
| | 2020 FBC FG SEC. 305.1. |
| | |
| | C. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG |
| | 410.1. |
| | |
| | D. WOULD YOU PLEASE SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER THE 2020 FBC FG SEC. 304.1, 614.5 (CLOTHES |
| | DRYERS AND TANK-LESS). IF A MECHANICAL COMBUSTION AIR |
| | SUPPLY SYSTEM AIR IS BEING SUPPLIED, PLEASE PROVIDE |
| | INFORMATION OR IF METAL LOUVERS ARE BEING INSTALLED FOR |
| | THE COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN |
| | EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF |
| | THE WALL MUST BE MAINTAINED. |
| | |
| | E. WOULD YOU PLEASE SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE |
| | ROOF, AND ANCHORING ELEMENTS OF THE GAS VENT(S) PER THE |
| | 2020 FBC FG SECS. 502 THRU 505. |
| | |
| | F. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC |
| | 410.2. |
| | |
| | G. IT SHOWS TWO WASHING MACHINES, BUT THERE ARE TWO |
| | DRYERS, AND IF THEY ARE STACKED, THE VALVES SHALL BE |
| | ACCESSIBLE WITHOUT MOVING THE EQUIPMENT PER THE 2020 |
| | FBC SEC. G2403 (202) GD, ACCESS. |
| | |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT. |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE CORRECTION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY |
| | PAGES. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |