2022-02-02 10:05:2502/02/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON RE-REVIEWING SUBMITTED CORRECTIONS.
  
 1. ON P04;
  
 A. THE BTU LOAD FOR THE WATER HEATER IS FOR A
 TANK-LESS, BUT THE PLAN SAYS AND SHOWS A TANK TYPE AND
 199 BTU'S ARE MOST TANK-LESS AND TANK TYPE ARE ABOUT 50
 BYU'S. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. WOULD YOU PLEASE SUBMIT MANUFACTURES SPECIFICATIONS
 FOR THE DRYER AND TANK-LESS TO VERIFY COMPLIANCE WITH
 2020 FBC FG SEC. 305.1.
  
 C. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG
 410.1.
  
 D. WOULD YOU PLEASE SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE 2020 FBC FG SEC. 304.1, 614.5 (CLOTHES
 DRYERS AND TANK-LESS). IF A MECHANICAL COMBUSTION AIR
 SUPPLY SYSTEM AIR IS BEING SUPPLIED, PLEASE PROVIDE
 INFORMATION OR IF METAL LOUVERS ARE BEING INSTALLED FOR
 THE COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED.
  
 E. WOULD YOU PLEASE SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF, AND ANCHORING ELEMENTS OF THE GAS VENT(S) PER THE
 2020 FBC FG SECS. 502 THRU 505.
  
 F. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC
 410.2.
  
 G. IT SHOWS TWO WASHING MACHINES, BUT THERE ARE TWO
 DRYERS, AND IF THEY ARE STACKED, THE VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE EQUIPMENT PER THE 2020
 FBC SEC. G2403 (202) GD, ACCESS.
  
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE CORRECTION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY
 PAGES. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  