Plan Review Notes
Plan Review Notes For Permit 22010437
Permit Number 22010437
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-25 15:43:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010437 205 DATURA ST # 405
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, CLARIFY MATERIAL
 SPECIFICATIONS. P0.1/NOTE 14 CALLS FOR TYPE L COPPER OR
 SDR 11 CPVC PIPING FOR WATER DISTRIBUTION. IF CPVC IS
 TO BE USED, PROVIDE SPECIFICATION FOR HANGERS AND OTHER
 COMPONENTS THAT ARE APPROVED BY THE MANUFACTURER FOR
 PHYSICAL CONTACT WITH THE SYSTEM. P0.1/NOTE 15 DOES NOT
 CLEARLY CALL FOR PVC BUT ALLUDES TO THE USE. PER WPB
 FBC 107.2.1, CLARIFY.
  
 2. P1.1/GENERAL NOTE 1; CONTRACTOR TO VERIFY IF TENANT
 CEILING SPACE BELOW IS A PLENUM AND PROVIDE CAST IRON
 INSTEAD OF PVC. PLEASE NOTE THAT THERE IS NO FIRE RATED
 FLOOR PENETRATION FOR METALLIC PIPE SHOWN ON P4.3. PER
 WPB FBC 107.2.1, PLEASE PROVIDE.
  
 3. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 4. P0.1/PLUMBING SCOPE NOTE 3 STATES ROUTE CONDENSATE
 DRAIN TO MECHANICAL ROOM DRAIN. P0.1/PLUMBING SCOPE
 NOTE 3 STATES CONDENSATE DRAIN TO ROUTE TO EXISTING
 CONDENSATE DRAIN IN MECHANICAL ROOM P1.1/KEYNOTE 3. PER
 WPB FBC 107.2.1, PLEASE MAKE P0.1/PLUMBING SCOPE NOTE 3
 AS CLEAR AS P0.1/PLUMBING SCOPE NOTE 3.
  
 5. P2.1/NOTE 4: PER FBC PL 606.1 (2), WATER SERVICE
 (FULL OPEN) VALVE SHALL BE INSTALLED AT THE ENTRANCE TO
 STRUCTURE. PROVIDE IN COMMON AREA WITH ACCESS PANEL
 RATED SAME AS THE CEILING.
  
 6. P4.1/WATER HEATER SCHEDULE: PROVIDE NOTE STATING
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL
 BE ON SITE PRIOR TO INSPECTION
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS