Plan Review Notes
Plan Review Notes For Permit 22010396
Permit Number 22010396
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-25 16:29:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010396 8225 IBIS BLVD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.AD101 DEMO FLOOR PLAN KEY NOTE D5 REFERS TO PLUMBING
 PLANS FOR TERMINATION OF WATER SUPPLY LINES AND
 DRAINPIPES; G1002 DRAWING INDEX LISTS P001 AND P002
 PLUMBING DRAWINGS. THERE HAVE BEEN NO PLUMBING DRAWINGS
 SUBMITTED. PER WPB FBC 107.2.1 PROVIDE PLUMBING
 DRAWINGS WITH CLEAR DIRECTION FOR TERMINATION OF SAID
 PIPES.
  
 2.PER WPB FBC 107.2.1, RECONCILE SUBMITTED DRAWINGS AND
 G1002 DRAWING INDEX.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  