2022-01-18 17:17:261ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010396
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101: KEYNOTE 1- PLEASE SEE FBC M TABLE
 403.3.1.1 FOOTNOTE H BELOW.
  
 2) THE PEDICURE STATIONS WILL NEED 50 CFM?S OF EXHAUST
 PER STATION. THE ROOM SHALL BE CALCULATED USING NAIL
 SALON IN TABLE 403.3.1.1.
  
 3) PLEASE SHOW THE REQUIRED EXHAUST FOR THE PEDICURE
 ROOM. FBC M TABLE 403.3.1.1
  
 4) PLEASE SHOW THE CORRECTED SUPPLY AIR FOR THE NEW
 PEDICURE ROOM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  