Plan Review Notes
Plan Review Notes For Permit 22010382
Permit Number 22010382
Review Stop G
Sequence Number 1
Notes
Date Text
2022-02-10 17:26:531ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22010382
 2/10/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A-7: THE RELOCATION OF THE GAS-FIRED TANKLESS WATER
 HEATER INTO THE BATHROOM IS PROHIBITED UNLESS THE UNIT
 IS A DIRECT-VENT APPLIANCE- SEC. G2406.2 FBC RES.
 PLEASE PROVIDE MORE INFORMATION INCLUDING THE MAKE AND
 MODEL OF THE WATER HEATER.
  
 2) A-7: PROVIDE A GAS PIPING PLAN AND RISER DRAWING-
 SEC. 107.3.5.3 WPB. THE RISER SHALL INCLUDE THE
 FOLLOWING DETAILS AND INFORMATION:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) BTU LOAD OF THE WATER HEATER.
 D) TYPES AND SIZE OF GAS PIPING.
 E) LOCATIONS OF REGULATOR, SHUTOFF VALVE, AND PIPE
 UNIONS.
 F) OUTLET PRESSURE AT REGULATOR.
 G) PIPE SIZING TABLE.
  
 3) A-7: COMBUSTION AIR AND VENTING PLANS ARE REQUIRED.
 FOR A DIRECT VENT UNIT SHOW THE TYPE AND SIZE OF INTAKE
 AND EXHAUST DUCTS, THE DUCT RUNS, AND TERMINATION
 LOCATIONS. ADDITIONAL COMMENTS MAY OCCUR DEPENDING ON
 THE TYPE OF UNIT BEING RELOCATED- SECS. G2407.1 &
 G2427.1 FBC RES.
  
 3) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  